| Mechanical | Original | D | 5/18/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2308887 |
| CO Springs DRE | Original | A | 5/15/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2307812 |
| Zoning/Planning | Original | / | 5/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2306242 |
| Plumbing | Original | D | 5/12/2026 | SHANEN | SHANEN | Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2306159 |
| Construction | Original | D | 5/12/2026 | DOUGC | DOUGC | Life Safety Plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2306148 |
| Submittal 2 | Original | / | 5/7/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2304539 |
| CO Springs Fire | Original | D | 4/29/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2300537 |
| CO Springs Hazmat | Original | N | 4/29/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2300536 |
| Energy | Original | D | 4/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2293004 |
| Mechanical | Original | D | 4/14/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2293003 |
| CO Springs DRE | Original | A | 4/13/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2292217 |
| Electrical | Original | D | 4/10/2026 | BERTHA | BERTHA | Provide all conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations pertaining to the scope of work. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide panel schedules with volt amps on all branch circuits and calculated load of panel in amps for all panels affected by the scope of work. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2291464 |
| Plumbing | Original | D | 4/9/2026 | SHANEN | SHANEN | Provide required water pipe size analysis data, see 2021 IPC appendix E. Data may be calculated from the point of connection. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2291234 |
| Zoning/Planning | Original | / | 4/9/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2291014 |
| CSU Water | Original | N | 4/9/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2290979 |
| CSU Waste Water | Original | N | 4/9/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2290977 |
| Construction | Original | D | 4/9/2026 | DOUGC | DOUGC | Accessibility // Life Safety Plan // Design Criteria * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2290938 |
| Electronic Plan | Original | / | 4/8/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2290568 |
| Electronic Plan | Original | / | 4/8/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2290244 |
| Enumeration | Original | N | 3/27/2026 | BECKYA | BECKYA | | | Enumeration | 2285729 |
| Electronic Plan | Original | / | 3/27/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2285719 |
| | Original | / | 3/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/27/2026 for plan submitted 03/26/2026. Submit Date updated to now. Plan now open for review. | | | 2285563 |
| Energy | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2285395 |
| Floodplain | Original | N | 3/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418308023) | | Floodplain | 2285393 |