| CO Springs Fire | Original | A | 5/12/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2306255 |
| CO Springs Hazmat | Original | N | 5/12/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2306254 |
| CO Springs DRE | Original | A | 4/29/2026 | SSADLER | SSADLER | Approved for a commercial interior remodel. No change is footprint, parking, or landscaping. The use change will have no fees owed. Use allowed per zone district. | | CO Springs DRE | 2300574 |
| Zoning/Planning | Original | / | 4/29/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2300534 |
| Energy | Original | D | 4/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2300222 |
| Mechanical | Original | D | 4/28/2026 | TREVORH | TREVORH | Disapproved; Need to provide the sequence of operation for the make up air and Hood exhaust interlocks * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2300221 |
| EPC Health Dept | Original | D | 4/28/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | EPC Health Dept | 2300146 |
| Construction | Original | A | 4/28/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2299805 |
| Electrical | Original | D | 4/27/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2299483 |
| Electronic Plan | Original | / | 4/27/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2299477 |
| Plumbing | Original | D | 4/24/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See clouded sections on additional requirements for 2021 IECC block. Provide required CSU variance letter for the indoor grease trap. Contact Robert Bowren at 719-668-1735 or fog@csu.org. CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Restroom location does not comply with section 403.3.1 and 403.3.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2298982 |
| CSU Water | Original | D | 4/24/2026 | CSUREVIEW | CSUREVIEW | Will re-review after GI sizing Form is reviewed. mjg | mgackle | CSU Water | 2298969 |
| CSU Waste Water | Original | D | 4/24/2026 | CSUREVIEW | CSUREVIEW | Submit a Grease Interceptor sizing form to verify GI size. mjg | mgackle | CSU Waste Water | 2298967 |
| Construction | Original | D | 4/24/2026 | BPHILLIPS | BPHILLIPS | Occupant load factor in customer waiting area. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2298876 |
| Electronic Plan | Original | / | 4/23/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2298331 |
| Enumeration | Original | N | 4/1/2026 | BRENT | BRENT | | | Enumeration | 2287656 |
| Electronic Plan | Original | / | 4/1/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2287643 |
| | Original | / | 4/1/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/01/2026 for plan submitted 03/31/2026. Submit Date updated to now. Plan now open for review. | | | 2287372 |
| Energy | Original | / | 3/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2287146 |
| Floodplain | Original | N | 3/31/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308412041) | | Floodplain | 2287145 |