| Energy | Original | D | 5/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2313005 |
| Electrical | Original | D | 5/28/2026 | CONNERM | CONNERM | Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Comply with 250.122. See one-line
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10. Show the VFD's on the one-line and provide their rated input current. 430.122(A) NEC.
Specify CU or AL. Alternates are not allowed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2313004 |
| Electronic Plan | Original | / | 5/26/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2311779 |
| Forest Lakes Waste Water | Original | D | 5/22/2026 | FORESTLAKES | FORESTLAKES | Plumbing – The waterjet cutter is directly connected to SW and the area also has a floor drain – both routes to sanitary sewer must be protected from accumulating particulates. While the cutter has a particulates filter, a sand interceptor must be installed in the floor drain to protect it from grit accumulation. | rnortonFLMD | Forest Lakes Waste Water | 2311063 |
| Forest Lakes Water | Original | D | 5/22/2026 | FORESTLAKES | FORESTLAKES | Site plan – please show how the old FH#6 lateral will be abandoned. Preferably, remove as much of old lateral as possible before capping. | rnortonFLMD | Forest Lakes Water | 2311064 |
| Monument Zoning | Original | A | 5/20/2026 | TOWNOFMON | TOWNOFMON | | Rey Medina | Monument Zoning | 2310155 |
| Mechanical | Original | D | 5/19/2026 | TREVORH | TREVORH | Disapproved; Need to provide the Natural Gas sheets with this submittal package. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2309328 |
| Electronic Plan | Original | / | 5/19/2026 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2309153 |
| Electronic Plan | Original | / | 5/11/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2305237 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | Your review was done using the 2021 International Fire Code and adopted amendments and policies of Monument Fire District. All permits can be applied for at monumentfire.org/permitsDeferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation.Field Verification Approved plans are subject to field verification. Installations not in accordance with approved plans or applicable codes may require correction.Inspection Scheduling All inspections shall be requested a minimum of 48 hours in advance through Monument Fire. Contact permits@monumentfire.org Approval by Monument Fire does not relieve the applicant from compliance with all other applicable codes, ordinances, and requirements from other agencies having jurisdiction. | SBenson9 | Monument Fire | 2303050 |
| Monument Hazmat | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | Inspection Scheduling All inspections shall be requested a minimum of 48 hours in advance through Monument Fire. Contact permits@monumentfire.org Approval by Monument Fire does not relieve the applicant from compliance with all other applicable codes, ordinances, and requirements from other agencies having jurisdiction.This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines.Deferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation. | SBenson9 | Monument Hazmat | 2303048 |
| Plumbing | Original | D | 5/1/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to the mechanical and electrical scope from the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping and condensate piping related items shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. Water heater schedule must show efficiency requirements are met per section C404.2. Water heater details must show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2301473 |
| Gas/Elec. Utils | Original | D | 5/1/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric or gas service territory. mjg | mgackle | Gas/Elec. Utils | 2301460 |
| Construction | Original | D | 5/1/2026 | SHELLEY | SHELLEY | See Code Study form, LSP, Floor plans, comcheck * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2301423 |
| Electronic Plan | Original | / | 4/30/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2301053 |
| Enumeration | Original | A | 4/7/2026 | BRENT | BRENT | | | Enumeration | 2290028 |
| Electronic Plan | Original | / | 4/7/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2290020 |
| | Original | / | 4/7/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/07/2026 for plan submitted 04/06/2026. Submit Date updated to now. Plan now open for review. | | | 2289883 |
| Water Division | Original | / | 4/6/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2289210 |
| Waste Water Div | Original | / | 4/6/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2289211 |
| Energy | Original | / | 4/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2289209 |
| Floodplain | Original | N | 4/6/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7135004003) | | Floodplain | 2289208 |