| CSU Water | Original | D | 7/23/2026 | CSUREVIEW | CSUREVIEW | Building connection points for water and wastewater service lines do not match between the plumbing plans and the USP. Please update so that the plans match. SSH | SHillman | CSU Water | 2338360 |
| CSU Waste Water | Original | D | 7/23/2026 | CSUREVIEW | CSUREVIEW | Building connection points for water and wastewater service lines do not match between the plumbing plans and the USP. Please update so that the plans match. SSH | SHillman | CSU Waste Water | 2338359 |
| Plumbing | Original | D | 7/23/2026 | SHANEN | SHANEN | FD does not comply with section 1101.3. 3/4" is undersized to serve downstream fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2337972 |
| Electronic Plan | Original | / | 7/23/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2337943 |
| | Original | / | 7/22/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2337828 |
| | Original | / | 7/22/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2337738 |
| Submittal 4 | Original | / | 7/22/2026 | TREYW | TREYW | Submittal #4 | | Submittal 4 | 2337737 |
| Plumbing | Original | D | 7/15/2026 | SHANEN | SHANEN | CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Shower draining to pool drainage system does not comply with section 301.3. Burial depth does not comply with section 305.4. 3/4" is undersized to serve downstream fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2334457 |
| CO Springs DRE | Original | A | 7/2/2026 | SSADLER | SSADLER | Proposed plans are consistent with the approved dp. | | CO Springs DRE | 2330351 |
| City Engr | Original | A | 7/1/2026 | DSOSA | DSOSA | EDRD has no additional comments | | City Engr | 2329553 |
| Mechanical | Original | A | 7/1/2026 | DALEH | DALEH | | | Mechanical | 2329526 |
| CSU Water | Original | D | 7/1/2026 | CSUREVIEW | CSUREVIEW | Approved USP must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Water | 2329459 |
| CSU Waste Water | Original | D | 7/1/2026 | CSUREVIEW | CSUREVIEW | Approved USP must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Waste Water | 2329455 |
| Gas/Elec. Utils | Original | A | 7/1/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2329453 |
| Electrical | Original | A | 7/1/2026 | CONNERM | CONNERM | | | Electrical | 2329386 |
| Zoning/Planning | Original | / | 7/1/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2329383 |
| Electronic Plan | Original | / | 7/1/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2329368 |
| Construction | Original | A | 7/1/2026 | SHELLEY | SHELLEY | Both buildings are unconditioned. | | Construction | 2329356 |
| Enumeration | Original | A | 6/30/2026 | BRENT | BRENT | | | Enumeration | 2328875 |
| Electronic Plan | Original | / | 6/30/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2328870 |
| | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2328858 |
| CSU Contract Admin. | Original | N | 6/30/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due this plane set. BS | bschifferstein | CSU Contract Admin. | 2328746 |
| | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2328514 |
| Submittal 3 | Original | / | 6/30/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2328513 |
| CO Springs Fire | Original | A | 6/24/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | phil.valdez | CO Springs Fire | 2326379 |
| CO Springs DRE | Original | D | 6/16/2026 | SSADLER | SSADLER | Development plan and approval letter will need to be uploaded to this permit. They were sent via email on 6-15-2026 | | CO Springs DRE | 2321634 |
| CSU Contract Admin. | Original | D | 6/5/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) under review. Payment of applicable utility charges and fees required. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate.BS | bschifferstein | CSU Contract Admin. | 2317342 |
| City Engr | Original | D | 6/5/2026 | HVO | HVO | Please see previous comment- include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2317249 |
| Mechanical | Original | A | 6/5/2026 | DALEH | DALEH | | | Mechanical | 2317189 |
| Plumbing | Original | D | 6/4/2026 | SHANEN | SHANEN | CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Clarify compliance with section 403.2. Burial depth does not comply with section 305.4. Lavatories must show compliance with 2021 IECC section C404.5.1. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Clarify how drain for outdoor shower is in compliance with section 1101.3. 3/4" is undersized to serve downstream fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2316626 |
| CSU Water | Original | D | 6/4/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Please upload the approved development plan and the approved USP to the plan set. PSD | PDosch | CSU Water | 2316564 |
| CSU Waste Water | Original | D | 6/4/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Please upload the approved development plan and the approved USP to the plan set. PSD | PDosch | CSU Waste Water | 2316562 |
| Gas/Elec. Utils | Original | D | 6/4/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Please upload the approved development plan to this plan set. PSD | PDosch | Gas/Elec. Utils | 2316557 |
| Zoning/Planning | Original | / | 6/4/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2316507 |
| Electrical | Original | D | 6/4/2026 | CONNERM | CONNERM | Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Panel A1 is overloaded * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2316475 |
| Construction | Original | D | 6/4/2026 | SHELLEY | SHELLEY | Still need separate code study form for pavilion. Per mechanical plans, heaters are being installed - provide IECC documents. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2316449 |
| Enumeration | Original | A | 6/3/2026 | BRENT | BRENT | | | Enumeration | 2316138 |
| Electronic Plan | Original | / | 6/3/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2316121 |
| Submittal 2 | Original | / | 6/3/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2316103 |
| CO Springs Fire | Original | D | 5/20/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2309602 |
| CO Springs Hazmat | Original | N | 5/19/2026 | CSFIRE | CSFIRE | Scope of work does not involve hazardous materials. sds | smitty91 | CO Springs Hazmat | 2309165 |
| Mechanical | Original | D | 5/15/2026 | DALEH | DALEH | Provide mechanical plans as needed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2307865 |
| CO Springs DRE | Original | D | 5/7/2026 | SSADLER | SSADLER | Case planner has reached out to the applicant on the height. Plans are denied until the case planner has received more information on the height. | | CO Springs DRE | 2304234 |
| Plumbing | Original | D | 5/6/2026 | SHANEN | SHANEN | Provide plumbing plans for the plumbing scope indicated on the architectural plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2303484 |
| Electrical | Original | N | 5/5/2026 | CONNERM | CONNERM | | | Electrical | 2303079 |
| Electronic Plan | Original | / | 5/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2303073 |
| Elevators | Original | N | 5/4/2026 | STEPHANIEV | STEPHANIEV | NO CONVEYANCES | | Elevators | 2302500 |
| CSU Contract Admin. | Original | D | 5/4/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and potential payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf BS | bschifferstein | CSU Contract Admin. | 2302278 |
| Zoning/Planning | Original | / | 5/4/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2302071 |
| CSU Water | Original | D | 5/1/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2301894 |
| CSU Waste Water | Original | D | 5/1/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2301893 |
| Gas/Elec. Utils | Original | D | 5/1/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2301891 |
| City Engr | Original | D | 5/1/2026 | HVO | HVO | Please include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2301888 |
| Construction | Original | D | 5/1/2026 | SHELLEY | SHELLEY | Occupant load, missing E/P plans, clarify heat for freeze protection, missing beam size. See plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2301858 |
| Electronic Plan | Original | / | 4/30/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2301277 |
| Enumeration | Original | A | 4/7/2026 | BRENT | BRENT | | | Enumeration | 2290063 |
| Electronic Plan | Original | / | 4/7/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2290057 |
| | Original | / | 4/7/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/07/2026 for plan submitted 04/07/2026. Submit Date updated to now. Plan now open for review. | | | 2290037 |
| Energy | Original | N | 4/7/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2289715 |
| Floodplain | Original | N | 4/7/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6316306318) | | Floodplain | 2289714 |