| Energy | Original | D | 5/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2307894 |
| Mechanical | Original | D | 5/15/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2307893 |
| CO Springs DRE | Original | A | 5/11/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2305309 |
| Electrical | Original | D | 5/7/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Bathroom lighting controls must be clearly shown and must comply with C405.2 (Interior) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2304269 |
| CO Springs Fire | Original | D | 5/7/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2304247 |
| CO Springs Hazmat | Original | N | 5/7/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2304245 |
| Electronic Plan | Original | / | 5/7/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2304240 |
| Plumbing | Original | D | 5/7/2026 | SHANEN | SHANEN | Provide plumbing plans for the indicated plumbing scope. No plumbing plans provided. Electrical plans were uploaded in the plumbing file. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2304226 |
| Zoning/Planning | Original | / | 5/6/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2304028 |
| Construction | Original | D | 5/6/2026 | BPHILLIPS | BPHILLIPS | Accessible route to restroom, wood in IIB construction. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2304016 |
| Electronic Plan | Original | / | 5/5/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2303240 |
| CSU Water | Original | D | 5/1/2026 | CSUREVIEW | CSUREVIEW | Electrical plans are present in the plumbing folder. Need to upload the plumbing plans for review. mjg | mgackle | CSU Water | 2301398 |
| CSU Waste Water | Original | D | 5/1/2026 | CSUREVIEW | CSUREVIEW | Electrical plans are present in the plumbing folder. Need to upload the plumbing plans for review. mjg | mgackle | CSU Waste Water | 2301397 |
| Enumeration | Original | D | 4/13/2026 | BECKYA | BECKYA | Plan was submitted under the wrong address. The address for this space is 1685 Briargate Parkway. Update all plan pages including the Code Study Form and MEP to show the correct address. Additionally, please provide Current secondary suite numbering for this building. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2292419 |
| Electronic Plan | Original | / | 4/13/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2292415 |
| | Original | / | 4/13/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/13/2026 for plan submitted 04/13/2026. Submit Date updated to now. Plan now open for review. | | | 2292406 |
| Energy | Original | / | 4/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2292154 |
| Floodplain | Original | N | 4/13/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6232102001) | | Floodplain | 2292153 |