| CSU Water | Original | A | 5/29/2026 | CSUREVIEW | CSUREVIEW | Comments addressed. CWMSF approved.MDA | malcuran | CSU Water | 2313995 |
| CSU Water | Original | / | 5/29/2026 | CSUREVIEW | CSUREVIEW | | malcuran | CSU Water | 2313994 |
| Mechanical | Original | D | 5/27/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2312266 |
| CO Springs Fire | Original | D | 5/26/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2312099 |
| CO Springs Hazmat | Original | D | 5/26/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2312098 |
| Electronic Plan | Original | / | 5/26/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2311837 |
| CO Springs DRE | Original | A | 5/7/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. Exterior changes are minor and will not require a modification. | | CO Springs DRE | 2304394 |
| Plumbing | Original | D | 5/7/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping and condensate piping related items shall be on the mechanical plans.Remove ALL references to gas piping and condensate piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Pool deck drains (trench drains in pool and spa area) must show compliance with section 802.1.4 and all 2021 ISPSC plumbing requirements. Provide required CSU variance letter for the indoor grease trap. Contact Robert Bowren at 719-668-1735 or fog@csu.org. CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. Controls and hand showers shall comply with ICC A117.1-2017 section 608.4. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2304341 |
| Electrical | Original | D | 5/6/2026 | CONNERM | CONNERM | Show compliance with 230.95
Provide fault current information in tabular form (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2303935 |
| Electronic Plan | Original | / | 5/6/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2303887 |
| CSU Water | Original | D | 5/6/2026 | CSUREVIEW | CSUREVIEW | Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL
***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.***Plumbing plans must specify the correct backflow device and show the correct meter configuration.MDA | malcuran | CSU Water | 2303807 |
| CSU Waste Water | Original | D | 5/6/2026 | CSUREVIEW | CSUREVIEW | Contact CSU Industrial Pretreatment representative Bob Bowren via email at fog@csu.org to determine if a variance for an interior grease interceptor is applicable. If applicable, provide a copy of the Variance letter in the building plan set.MDA | malcuran | CSU Waste Water | 2303804 |
| EPC Health Dept | Original | D | 5/6/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2303773 |
| Zoning/Planning | Original | / | 5/6/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2303489 |
| Energy | Original | N | 5/6/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2303486 |
| Construction | Original | D | 5/6/2026 | DOUGC | DOUGC | Accessibility // Design Criteria * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2303485 |
| Electronic Plan | Original | / | 5/5/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2303335 |
| Enumeration | Original | D | 4/15/2026 | AMY | AMY | The vicinity map is blurry and is not legible. The area was recently replatted and the legal description has changed. Update the above information. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2293175 |
| Electronic Plan | Original | / | 4/15/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2293142 |
| | Original | / | 4/14/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/14/2026 for plan submitted 04/13/2026. Submit Date updated to now. Plan now open for review. | | | 2293121 |
| Energy | Original | / | 4/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2292315 |
| Floodplain | Original | N | 4/13/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6430122005) | | Floodplain | 2292314 |