| Mechanical | Original | D | 5/26/2026 | TREVORH | TREVORH | Disapproved; Need to upload the Entire Mechanical submittal package the Clouds are to identify changes or additions to the plans. If Mechanical equipment is being re used this needs to be noted in the schedules as (E) existing. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2311838 |
| Plumbing | Original | A | 5/26/2026 | SHANEN | SHANEN | | | Plumbing | 2311750 |
| Electrical | Original | D | 5/26/2026 | CONNERM | CONNERM | Provide electrical plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2311552 |
| Construction | Original | D | 5/26/2026 | SHELLEY | SHELLEY | Incorrect structural design loads * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2311539 |
| Submittal 2 | Original | / | 5/22/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2311420 |
| CO Springs Fire | Original | D | 5/20/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2309760 |
| CO Springs Hazmat | Original | D | 5/20/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2309759 |
| Mechanical | Original | D | 5/7/2026 | TREVORH | TREVORH | Disapproved; Mechanical submittal package is missing the Natural Gas plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2304476 |
| Plumbing | Original | D | 5/7/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. All accessibility requirements shall be per ICC A117.1-2017. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2304168 |
| CO Springs DRE | Original | A | 5/5/2026 | SSADLER | SSADLER | Approved for commercial interior remodel and proposed facade changes. No changes to parking, landscaping, or use. | | CO Springs DRE | 2303327 |
| City Engr | Original | N | 5/4/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2302621 |
| Zoning/Planning | Original | / | 5/4/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2302533 |
| CSU Water | Original | N | 5/4/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 2302532 |
| CSU Waste Water | Original | N | 5/4/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 2302530 |
| Gas/Elec. Utils | Original | A | 5/4/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2302525 |
| Electrical | Original | D | 5/4/2026 | CONNERM | CONNERM | Provide total demand load of panels in amps
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide conductor size, type, quantity on one-line * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2302524 |
| Electronic Plan | Original | / | 5/4/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2302489 |
| Energy | Original | N | 5/4/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2302485 |
| Construction | Original | A | 5/4/2026 | DOUGC | DOUGC | | | Construction | 2302484 |
| Electronic Plan | Original | / | 5/2/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2302020 |
| Plumbing | Original | / | 4/17/2026 | DANM | DANM | Overtime approved for Plumbing by Jaimee Lee Stoddard | | Plumbing | 2294887 |
| Mechanical | Original | / | 4/17/2026 | DANM | DANM | Overtime approved for Mechanical by Jaimee Lee Stoddard | | Mechanical | 2294886 |
| Electrical | Original | / | 4/17/2026 | DANM | DANM | Overtime approved for Electrical by Jaimee Lee Stoddard | | Electrical | 2294885 |
| Construction | Original | / | 4/17/2026 | DANM | DANM | Overtime approved for Construction by Jaimee Lee Stoddard | | Construction | 2294884 |
| Enumeration | Original | N | 4/15/2026 | BECKYA | BECKYA | | | Enumeration | 2293164 |
| Electronic Plan | Original | / | 4/15/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2293151 |
| | Original | / | 4/15/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/15/2026 for plan submitted 04/14/2026. Submit Date updated to now. Plan now open for review. | | | 2293143 |
| Energy | Original | / | 4/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2293126 |
| Floodplain | Original | N | 4/14/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6232102001) | | Floodplain | 2293125 |