| CO Springs Fire | Original | D | 6/1/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2314833 |
| CO Springs Hazmat | Original | N | 6/1/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2314832 |
| Energy | Original | D | 5/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2309392 |
| Mechanical | Original | D | 5/19/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2309391 |
| CO Springs DRE | Original | D | 5/18/2026 | SSADLER | SSADLER | This is in the hillside overlay. Schedule a pre application meeting to discuss proposed exterior changes with the case planner | | CO Springs DRE | 2308455 |
| Stormwater | Original | D | 5/15/2026 | JLANDON | JLANDON | upload a development plan and Stormwater Grading and Erosion Control Plan if applicable. otherwise a hillside development plan will be required.
Hillside plan stormwater checklist: 1. LOD 2. Existing and proposed contour lines (they should have labels) 3. Legend 4. Stockpile - it must be inside the LOD 5. Flow arrows 6. PE signature and stamp 7. Overall grading - will water drain appropriately and not pool badly (e.g. against a building)? | | Stormwater | 2308176 |
| City Engr | Original | D | 5/14/2026 | HVO | HVO | Please upload the approved Development Plan (If applicable). EDRD has determined geological hazards exist in this area and requires a Geologic Hazard Report. Please submit it to EDRD through our electronic review system called ProjectDox. Below is a link to ProjectDox and a user manual. https://coloradosprings.gov/stormwater/planreview
Once it has been approved please upload the approved file with building submission. | | City Engr | 2307219 |
| Zoning/Planning | Original | / | 5/13/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2307073 |
| CSU Water | Original | N | 5/13/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2307029 |
| CSU Waste Water | Original | N | 5/13/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2307028 |
| Gas/Elec. Utils | Original | N | 5/13/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. MLW | mlwilliams | Gas/Elec. Utils | 2307026 |
| Electrical | Original | D | 5/13/2026 | CONNERM | CONNERM | Fault current information (SCCR, AIC, SCA) at all refed/relocated panels
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Show compliance with C405.11 or have approved AM&M at time of submittal * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2306843 |
| Electronic Plan | Original | / | 5/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2306806 |
| Plumbing | Original | D | 5/13/2026 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403. 3/4" DCW is undersized to serve 2-WC1 and 2-L1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2306805 |
| Construction | Original | D | 5/13/2026 | DOUGC | DOUGC | CSF // LSP // OCC LOAD * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2306793 |
| Enumeration | Original | D | 5/13/2026 | BECKYA | BECKYA | Verify if this will be a single tenant, if so, remove Suite A from the address. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2306745 |
| Electronic Plan | Original | / | 5/13/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2306662 |
| Enumeration | Original | N | 4/27/2026 | BECKYA | BECKYA | | | Enumeration | 2299639 |
| Electronic Plan | Original | / | 4/27/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2299628 |
| | Original | / | 4/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/27/2026 for plan submitted 04/24/2026. Submit Date updated to now. Plan now open for review. | | | 2299614 |
| Energy | Original | / | 4/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2298530 |
| Floodplain | Original | N | 4/24/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6307306063) | | Floodplain | 2298529 |