| Electrical | Original | D | 4/30/2026 | BERTHA | BERTHA | Provide footprint (site plan) showing all electrical service equipment and disconnects serving the structure
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC). . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2301208 |
| Energy | Original | D | 4/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2301209 |
| Mechanical | Original | D | 4/30/2026 | TREVORH | TREVORH | Disapproved; Plan is showing RTU's as existing, schedule on M0.1 is showing New RTU's. If new are being installed remove existing from plans and Revise the MECHANICALcomcheck * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2301155 |
| CO Springs DRE | Original | A | 4/29/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No exterior changes | | CO Springs DRE | 2300635 |
| CO Springs Fire | Original | A | 4/29/2026 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance.
CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2300599 |
| CO Springs Hazmat | Original | N | 4/29/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2300598 |
| City Engr | Original | N | 4/28/2026 | HVO | HVO | | | City Engr | 2300077 |
| CSU Contract Admin. | Original | N | 4/28/2026 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and applicable Development fees/charges paid - master meter configuration. AMS | ASweet | CSU Contract Admin. | 2300019 |
| Zoning/Planning | Original | / | 4/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2299921 |
| Plumbing | Original | D | 4/28/2026 | SHANEN | SHANEN | Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Provide a water heater installation detail. Water heater detail must show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. ST-5 is for residential use only per manufacturer. Show compliance with chapter 9. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2299913 |
| Gas/Elec. Utils | Original | N | 4/28/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. DMM | dmakings | Gas/Elec. Utils | 2299902 |
| CSU Waste Water | Original | N | 4/28/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2299901 |
| CSU Water | Original | N | 4/28/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2299900 |
| Construction | Original | A | 4/28/2026 | BPHILLIPS | BPHILLIPS | Deleted note in question, per submitter. | | Construction | 2299876 |
| Construction | Original | D | 4/28/2026 | BPHILLIPS | BPHILLIPS | Clarify note page 4 architectural sheets. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2299852 |
| Electronic Plan | Original | / | 4/27/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2299294 |
| Enumeration | Original | A | 4/27/2026 | AMY | AMY | | | Enumeration | 2299203 |
| Electronic Plan | Original | / | 4/27/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2299191 |
| | Original | / | 4/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/24/2026 for plan submitted 04/24/2026. Submit Date updated to now. Plan now open for review. | | | 2299052 |
| Energy | Original | / | 4/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2298569 |
| Floodplain | Original | N | 4/24/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220201044) | | Floodplain | 2298567 |