| Electrical | Original | A | 6/17/2026 | CONNERM | CONNERM | | | Electrical | 2322595 |
| CO Springs DRE | Original | A | 6/17/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2322540 |
| Electrical | Original | D | 6/17/2026 | CONNERM | CONNERM | Open office must comply with IECC C405.11 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2322530 |
| Electronic Plan | Original | / | 6/17/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2322520 |
| Zoning/Planning | Original | / | 6/17/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2322445 |
| Mechanical | Original | A | 6/17/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2322440 |
| Construction | Original | A | 6/17/2026 | BRIANB | BRIANB | | | Construction | 2322408 |
| Enumeration | Original | D | 6/16/2026 | AMY | AMY | See comments from 4/27/26 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2321910 |
| Electronic Plan | Original | / | 6/16/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2321900 |
| Submittal 2 | Original | / | 6/16/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2321742 |
| CO Springs Fire | Original | D | 6/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2318906 |
| CO Springs Hazmat | Original | N | 6/10/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2318905 |
| CO Springs DRE | Original | A | 5/20/2026 | CHUDSPETH | CHUDSPETH | Interior commercial remodel, no change of use or occupancy. | | CO Springs DRE | 2309736 |
| Zoning/Planning | Original | / | 5/20/2026 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2309734 |
| Mechanical | Original | D | 5/18/2026 | TREVORH | TREVORH | Disapproved; Need to provide the Refrigeration calculation for the mini split * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2309064 |
| CSU Water | Original | N | 5/18/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2308891 |
| CSU Waste Water | Original | N | 5/18/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2308889 |
| Electrical | Original | D | 5/18/2026 | CONNERM | CONNERM | Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1.All new air conditioning and refrigeration equipment
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Fully comply with IECC C405.11 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2308601 |
| Electronic Plan | Original | / | 5/18/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2308561 |
| Plumbing | Original | A | 5/18/2026 | SHANEN | SHANEN | | | Plumbing | 2308560 |
| Construction | Original | D | 5/18/2026 | BRIANB | BRIANB | See sheets G0-01 / INo-01 / IN8-00 / IN8-03 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2308506 |
| Energy | Original | N | 5/15/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2308286 |
| Energy | Original | / | 5/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2308284 |
| Electronic Plan | Original | / | 5/15/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2308127 |
| Enumeration | Original | D | 4/27/2026 | AMY | AMY | The permit history on this building is dated. Please add the suite numbers to this floor plan to sheet G0-01. This is suite 150. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2299539 |
| Electronic Plan | Original | / | 4/27/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2299496 |
| | Original | / | 4/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/27/2026 for plan submitted 04/27/2026. Submit Date updated to now. Plan now open for review. | | | 2299467 |
| Energy | Original | / | 4/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2299446 |
| Floodplain | Original | N | 4/27/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233108051) | | Floodplain | 2299445 |