| Energy | Original | A | 6/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2318276 |
| Mechanical | Original | A | 6/9/2026 | DALEH | DALEH | | | Mechanical | 2318275 |
| Plumbing | Original | A | 6/9/2026 | SHANEN | SHANEN | | | Plumbing | 2318222 |
| | Original | / | 6/9/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2318200 |
| | Original | / | 6/9/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2318165 |
| Submittal 3 | Original | / | 6/9/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2318164 |
| Energy | Original | D | 6/8/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2317605 |
| Mechanical | Original | D | 6/8/2026 | DALEH | DALEH | When evaporative cooler is not in use in the winter how will the system stop cold air from migrating into the building ? See IECC 2021 C403.7.7 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2317604 |
| Gas/Elec. Utils | Original | A | 6/8/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 2317498 |
| Gas/Elec. Utils | Original | A | 6/8/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 2317497 |
| Plumbing | Original | D | 6/8/2026 | SHANEN | SHANEN | Provide an automatic drain and fill kit for each evaporative cooler per mechanical plans. In this jurisdiction all water lines subject to freezing conditions require both insulation and heat. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2317369 |
| Submittal 2 | Original | / | 6/5/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2317272 |
| Energy | Original | D | 5/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2309444 |
| Mechanical | Original | D | 5/19/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2309443 |
| County Zoning | Original | N | 5/7/2026 | DSDRANGEL | DSDRANGEL | | | County Zoning | 2304328 |
| Zoning/Planning | Original | / | 5/7/2026 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 2304323 |
| Plumbing | Original | D | 5/7/2026 | SHANEN | SHANEN | DCW serving EVAP 1&2 must show compliance with section 305.4 and 608.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2304173 |
| Electrical | Original | A | 5/6/2026 | CONNERM | CONNERM | | | Electrical | 2304071 |
| Electronic Plan | Original | / | 5/6/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2304060 |
| Gas/Elec. Utils | Original | D | 5/6/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' gas service territory. MDA | malcuran | Gas/Elec. Utils | 2304052 |
| Construction | Original | N | 5/6/2026 | SHELLEY | SHELLEY | No construction scope | | Construction | 2304038 |
| Floodplain | Original | N | 5/5/2026 | KEITH | KEITH | | | Floodplain | 2303423 |
| Enumeration | Original | N | 5/5/2026 | BECKYA | BECKYA | | | Enumeration | 2303379 |
| | Original | / | 5/5/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/05/2026 for plan submitted 05/04/2026. Submit Date updated to now. Plan now open for review. | | | 2303329 |
| Energy | Original | / | 5/4/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2302610 |
| Floodplain | Original | / | 5/4/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 2202400002) | | Floodplain | 2302607 |