| CO Springs Fire | Original | D | 6/29/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2328430 |
| CO Springs Hazmat | Original | N | 6/29/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2328429 |
| Energy | Original | D | 6/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2318272 |
| Mechanical | Original | D | 6/9/2026 | TREVORH | TREVORH | Disapproved; Natural Gas piping plan is missing from the Mechanical submittal package * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2318271 |
| Plumbing | Original | D | 6/5/2026 | SHANEN | SHANEN | Preliminary review. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping and condensate piping related items shall be on the mechanical plans. Remove ALL references to gas piping and condensate piping from the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Reference 2021 IPC. Remove all references to perimeter foundation drain piping from the plumbing plans. Provide DWV and water distribution isometric drawings. Elevator sump discharge must show compliance with section 301.6 Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft, provided that they are indirectly connected to the plumbing system. Discharge elevator sump indirectly to a waste receptor capable of handling a minimum of 50 gpm (100 dfu). Water heater detail must show compliance with IECC section C404.3. DF-1B does not comply with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2316926 |
| CO Springs DRE | Original | D | 6/5/2026 | SSADLER | SSADLER | The modification to the development plan is still under review. Once it is approved, upload the approval letter and the approved stamped plan set. | | CO Springs DRE | 2316902 |
| Electrical | Original | D | 6/4/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11
Provide fault current information (SCCR, AIC, SCA) at all of the following locations. TERMS AND METHODOLOGIES section below. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide panel schedule for MSB * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2316595 |
| Electronic Plan | Original | / | 6/4/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2316558 |
| Elevators | Original | N | 6/4/2026 | STEPHANIEV | STEPHANIEV | NO CONVEYANCES | | Elevators | 2316448 |
| City Engr | Original | D | 6/3/2026 | HVO | HVO | Please see previous comment- include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2316095 |
| CSU Contract Admin. | Original | D | 6/3/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and potential payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2315942 |
| CSU Water | Original | D | 6/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 2315760 |
| CSU Waste Water | Original | D | 6/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2315759 |
| Gas/Elec. Utils | Original | D | 6/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2315757 |
| Zoning/Planning | Original | / | 6/3/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2315603 |
| Construction | Original | A | 6/2/2026 | DOUGC | DOUGC | | | Construction | 2315540 |
| Energy | Original | / | 6/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2315539 |
| Electronic Plan | Original | / | 6/2/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2315493 |
| Enumeration | Original | N | 5/28/2026 | BRENT | BRENT | | | Enumeration | 2313726 |
| Electronic Plan | Original | / | 5/28/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2313705 |
| | Original | / | 5/28/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/28/2026 for plan submitted 05/12/2026. Submit Date updated to now. Plan now open for review. | | | 2313293 |
| Energy | Original | / | 5/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2306266 |
| Floodplain | Original | N | 5/12/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6313001057) | | Floodplain | 2306264 |