| CO Springs Fire | Original | A | 7/2/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2330330 |
| CO Springs Hazmat | Original | N | 7/2/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2330328 |
| Energy | Original | D | 6/8/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2317556 |
| Mechanical | Original | D | 6/8/2026 | DALEH | DALEH | Remove coloring from plan and add a point of connection symbol each place new duct attaches to existing duct Indicate on floor plan the sizes of the round pipe not just in diffuser schedule typical Is this suppose to be a transfer fan ?Labeling as exhaust fan it must discharge to the exterior See plans for all comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2317555 |
| Plumbing | Original | D | 6/5/2026 | SHANEN | SHANEN | Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Remove all references to PAM HEALTH REHAB HOSPITAL OF CYPRESS TEXAS. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2317179 |
| Electrical | Original | D | 6/5/2026 | CONNERM | CONNERM | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards
Comply with C405.11 IECC in all applicable areas-See power plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2316889 |
| Electronic Plan | Original | / | 6/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2316876 |
| CSU Waste Water | Original | D | 6/5/2026 | CSUREVIEW | CSUREVIEW | Wastewater plan will be be reviewed again when updated documents and revised plan are resubmitted. Please clearly label connection to existing wastewater service and indicate if any changes to service outside of the building are being proposed. PSD | PDosch | CSU Waste Water | 2316864 |
| CSU Water | Original | D | 6/5/2026 | CSUREVIEW | CSUREVIEW | Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.*** Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form can be found at: https://www.csu.org/Documents/DomesticAssembly.pdf?csf=1&e=KLQNrS ***Form must be submitted to crossconnection@csu.org. PSD | PDosch | CSU Water | 2316859 |
| Energy | Original | / | 6/4/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2316728 |
| Construction | Original | D | 6/4/2026 | MATTHEWA | MATTHEWA | Code Study Form // Life Safety Plan // Occupant Loads // IECC Form // Fire Rated Corridors * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2316690 |
| Electronic Plan | Original | / | 6/4/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2316299 |
| Enumeration | Original | N | 5/15/2026 | AMY | AMY | | | Enumeration | 2308106 |
| Electronic Plan | Original | / | 5/15/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2308101 |
| | Original | / | 5/15/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/15/2026 for plan submitted 05/15/2026. Submit Date updated to now. Plan now open for review. | | | 2308094 |
| Energy | Original | / | 5/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2308025 |
| Floodplain | Original | N | 5/15/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6330102027) | | Floodplain | 2308024 |