| CO Springs DRE | Original | A | 6/10/2026 | CHUDSPETH | CHUDSPETH | Interior commercial remodel, no change of use or occupancy. | | CO Springs DRE | 2318765 |
| Zoning/Planning | Original | / | 6/10/2026 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2318764 |
| EPC Health Dept | Original | D | 6/9/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2318167 |
| Plumbing | Original | D | 6/8/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to Florida building agencies. Remove all references to Ohio codes. Provide code path/section that supports discharging a hand sink and dump sink through an indirect waste connection. Show piping to point of connection and sizing at POC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2317733 |
| CSU Water | Original | N | 6/8/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2317610 |
| CSU Waste Water | Original | N | 6/8/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2317609 |
| Zoning/Planning | Original | / | 6/8/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2317587 |
| Electrical | Original | D | 6/8/2026 | CONNERM | CONNERM | Show all electrical service equipment and disconnects serving the structure on floor plan
Provide panel schedules with Volt amps on all branch circuits and calculated load of panel in amps
Provide one-line
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2317578 |
| Electronic Plan | Original | / | 6/8/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2317535 |
| Mechanical | Original | D | 6/8/2026 | DALEH | DALEH | Provide mechanical plans as indicated on code study * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2317526 |
| Construction | Original | D | 6/8/2026 | BPHILLIPS | BPHILLIPS | Egress width factors, wall types * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2317522 |
| Energy | Original | N | 6/5/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2316899 |
| Electronic Plan | Original | / | 6/5/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2316844 |
| Enumeration | Original | N | 5/21/2026 | BECKYA | BECKYA | | | Enumeration | 2310878 |
| Electronic Plan | Original | / | 5/21/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2310862 |
| | Original | / | 5/21/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/21/2026 for plan submitted 05/18/2026. Submit Date updated to now. Plan now open for review. | | | 2310851 |
| Energy | Original | / | 5/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2308585 |
| Floodplain | Original | N | 5/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418214001) | | Floodplain | 2308584 |