| | Original | / | 7/24/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2338946 |
| | Original | / | 7/24/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2338909 |
| Submittal 3 | Original | / | 7/24/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2338908 |
| CO Springs DRE | Original | A | 7/20/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2336362 |
| Mechanical | Original | D | 7/17/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2335566 |
| Electrical | Original | D | 7/17/2026 | CONNERM | CONNERM | Provide fault current information (SCCR, AIC, SCA) for new air conditioning equipment * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2335542 |
| Zoning/Planning | Original | / | 7/17/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2335531 |
| Electronic Plan | Original | / | 7/17/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2335517 |
| Construction | Original | A | 7/17/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2335507 |
| Submittal 2 | Original | / | 7/16/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2335128 |
| CO Springs Fire | Original | A | 7/8/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2331663 |
| CO Springs Hazmat | Original | N | 7/8/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2331662 |
| Gas/Elec. Utils | Original | A | 6/11/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final electric meter, transformer and service line locations. Contact Field Engineering at 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2319654 |
| CSU Water | Original | N | 6/11/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2319652 |
| CSU Waste Water | Original | N | 6/11/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2319650 |
| CO Springs DRE | Original | A | 6/10/2026 | CHUDSPETH | CHUDSPETH | Interior commercial remodel, no change of use or occupancy. | | CO Springs DRE | 2319141 |
| Zoning/Planning | Original | / | 6/10/2026 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2319140 |
| Plumbing | Original | N | 6/10/2026 | SHANEN | SHANEN | No plumbing plans provided. No plumbing scope indicated. | | Plumbing | 2318882 |
| Mechanical | Original | D | 6/10/2026 | DALEH | DALEH | Show complete condensate routing and size Either provide a roof plan or indicate on drawings roof hatch, flat roof ETC..... All sheets are required to have the design professionals stamp See plans for all comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2318784 |
| Electrical | Original | D | 6/10/2026 | CONNERM | CONNERM | Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2318756 |
| Electronic Plan | Original | / | 6/10/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2318742 |
| Construction | Original | D | 6/10/2026 | BPHILLIPS | BPHILLIPS | Life safety plan, code study form * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2318697 |
| Energy | Original | N | 6/8/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2317820 |
| Electronic Plan | Original | / | 6/8/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2317675 |
| Enumeration | Original | N | 5/21/2026 | BRENT | BRENT | | | Enumeration | 2310607 |
| Floodplain | Original | N | 5/21/2026 | BRENT | BRENT | | | Floodplain | 2310606 |
| Electronic Plan | Original | / | 5/21/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2310590 |
| | Original | / | 5/21/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/21/2026 for plan submitted 05/19/2026. Submit Date updated to now. Plan now open for review. | | | 2310514 |
| Energy | Original | / | 5/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2309342 |
| Floodplain | Original | / | 5/19/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6305401039) | | Floodplain | 2309341 |