| Finished Bin (Main) | Original | / | 8/27/2026 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2352932 |
| Plumbing | Original | A | 8/26/2026 | SHANEN | SHANEN | | | Plumbing | 2352764 |
| | Original | / | 8/26/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2352744 |
| | Original | / | 8/24/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2351559 |
| Submittal 3 | Original | / | 8/24/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2351558 |
| EPC Health Dept | Original | N | 8/20/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable.GGM | Heagmiranda | EPC Health Dept | 2350526 |
| Plumbing | Original | D | 8/12/2026 | SHANEN | SHANEN | Dump sink shall discharge through a direct waste connection. Food waste disposer does not comply with section 416. Note: Food waste disposers are permitted to discharge through a minimum 500 gallon grease interceptor per state amendment. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2346903 |
| Out to Review | Original | / | 8/12/2026 | NICOLASV | NICOLASV | Jamie 719-306-8766 | | Out to Review | 2346871 |
| Finished Bin (Main) | Original | / | 7/30/2026 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2340991 |
| Plan Coordinator (Main) | Original | / | 7/29/2026 | | SHANEN | Location = Plan Coordinator (Main) by SHANEN | | Plan Coordinator (Main) | 2340356 |
| Plumbing | Original | D | 7/29/2026 | SHANEN | SHANEN | Engineer of record must stamp/sign code study form. Provide code path/section that supports discharging a dump sink through an indirect waste connection. Scheduled garbage disposal connection must show compliance with section 416.3. Show a direct waste connection for DS. DS must show compliance with section 1003.3.1. See CCR exception to section 1003.2.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2340355 |
| Out to Review | Original | / | 7/28/2026 | NELIDA | NELIDA | Jamie 719-306-8766 | | Out to Review | 2340263 |
| Finished Bin (Main) | Original | / | 7/28/2026 | | NELIDA | Location = Finished Bin (Main) by NELIDA | | Finished Bin (Main) | 2339971 |
| CSU Water | Original | N | 7/28/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow okay.MDA | malcuran | CSU Water | 2339945 |
| CSU Waste Water | Original | N | 7/28/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2339944 |
| CSU Utilities | Original | / | 7/28/2026 | | SCANNING | Location = CSU Utilities by SCANNING | | CSU Utilities | 2339857 |
| Plan Coordinator (Main) | Original | / | 7/27/2026 | | SHANEN | Location = Plan Coordinator (Main) by SHANEN | | Plan Coordinator (Main) | 2339380 |
| Plumbing | Original | D | 7/27/2026 | SHANEN | SHANEN | Provide disapproved plans for comparison. Engineer of record must stamp/sign code study form. Provide code path/section that supports discharging a dump sink through an indirect waste connection. Scheduled garbage disposal connection must show compliance with section 416.3. Show a direct waste connection for DS. DS must show compliance with section 1003.3.1. See CCR exception to section 1003.2.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2339378 |
| CSU Utilities | Original | / | 7/27/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | CSU Utilities | 2339347 |
| CSU Utilities | Original | / | 7/24/2026 | | JANE | Location = CSU Utilities by JANE | | CSU Utilities | 2339118 |
| Plan Coordinator (Main) | Original | / | 7/24/2026 | | MELISSAF | Location = Plan Coordinator (Main) by MELISSAF | | Plan Coordinator (Main) | 2339110 |
| | Original | / | 7/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/24/2026 for plan submitted 07/23/2026 | | | 2339109 |
| Submittal 2 | Original | / | 7/23/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2338549 |
| Plumbing | Original | D | 5/20/2026 | SHANEN | SHANEN | EOR must redraw the plumbing plans. CSU variance letter required for the indoor grease trap. Schedule the grease trap based on CSU requirements. Schedule sewage ejector and pit. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2309993 |
| Construction | Original | N | 5/20/2026 | JUSTINL | JUSTINL | No construction in scope of work. Plans show plumbing only | | Construction | 2309971 |
| Enumeration | Original | N | 5/20/2026 | BECKYA | BECKYA | | | Enumeration | 2309966 |
| Out to Review | Original | / | 5/19/2026 | QUINTONW | QUINTONW | Shawna Walking 7196401417 | | Out to Review | 2309436 |
| Energy | Original | N | 5/19/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2309420 |
| Floodplain | Original | N | 5/19/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6331409018) | | Floodplain | 2309419 |