| CO Springs Hazmat | Original | D | 7/13/2026 | CSFIRE | CSFIRE | DFM-C-CG-26-00034 Need refrigeration information; see M-101. Need CO2 auto shutoff and specification sheets; see CO1.01. May request a deferred submittal for the CO2. You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | mark.stanwood@colora | CO Springs Hazmat | 2333496 |
| CO Springs Fire | Original | A | 7/8/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION!
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | Jacob.Watson | CO Springs Fire | 2332094 |
| EPC Health Dept | Original | A | 6/18/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment was pre-approved (with conditions)in plan review. A pre-operational inspection will be required before final approval for opening is granted. MT | mtemple | EPC Health Dept | 2323458 |
| Energy | Original | D | 6/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2323233 |
| Mechanical | Original | D | 6/18/2026 | TREVORH | TREVORH | Disapproved; Need to provide the Refrigeration Calculations for the Walk in cooler/Freezer or state in Keyed Notes Sensors and alarms will be required.show condensate drain line routing on plans for the coolers * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2323232 |
| Electrical | Original | D | 6/16/2026 | CONNERM | CONNERM | Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
"Team Member Room" Must comply with C405.11
MDP is overloaded
MDP Panel schedule shows 65,000 AIC. Please clarify on shot circuit schedule
Plan shows 5 RTUs. Show AIC and ISC for individual RTUs
Show compliance with 240.87 and 230.95 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2321864 |
| CO Springs DRE | Original | D | 6/16/2026 | SSADLER | SSADLER | Upload the final approved and stamped development plan. Upload the final approved landscaping and irrigation plans. Upload the approval letter. Upload the final recorded plat. Fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2321847 |
| Electronic Plan | Original | / | 6/16/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2321785 |
| City Engr | Original | D | 6/15/2026 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set.
Please submit financial assurances for all public street improvements along Straight Way. These must be posted prior to building permit issuance by City Engineering. In addition, public street construction plans must be submitted separately to Engineering Development Review and Traffic Engineering and reviewed/approved prior to beginning of construction of all public right-of-way improvements. Thank you. | | City Engr | 2321131 |
| EPC Health Dept | Original | D | 6/12/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH.
Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. KB
For questions, contact Environmental Health at 719-578-3199 option 3. | KBauer | EPC Health Dept | 2320622 |
| Plumbing | Original | D | 6/12/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, grease interceptor location, etc. Show 2" CW and 3/4" CW extended to a minimum of 30" beyond the exterior walls. Provide roof plan to show sizing for roof drain conductors, downspouts and overflow scuppers. Provide gpm and/or square footage served by components of the roof drain system. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2320565 |
| Elevators | Original | N | 6/12/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2320485 |
| CSU Contract Admin. | Original | D | 6/12/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. JMD | jdemello | CSU Contract Admin. | 2320451 |
| CSU Water | Original | D | 6/12/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Water | 2320393 |
| CSU Waste Water | Original | D | 6/12/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Waste Water | 2320392 |
| Gas/Elec. Utils | Original | D | 6/12/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | Gas/Elec. Utils | 2320390 |
| Zoning/Planning | Original | / | 6/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2320324 |
| Construction | Original | D | 6/12/2026 | MATTHEWA | MATTHEWA | Cover sheet // Life Safety Plan // Structural details // Door hardware // Code Study Form // Occupant Load // Outdoor seating area * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2320281 |
| Electronic Plan | Original | / | 6/10/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2318929 |
| Enumeration | Original | A | 5/21/2026 | BRENT | BRENT | | | Enumeration | 2310925 |
| Electronic Plan | Original | / | 5/21/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2310906 |
| | Original | / | 5/21/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/21/2026 for plan submitted 05/21/2026. Submit Date updated to now. Plan now open for review. | | | 2310636 |
| Energy | Original | / | 5/21/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2310610 |
| Floodplain | Original | N | 5/21/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5310209011) | | Floodplain | 2310609 |