| CO Springs Fire | Original | D | 7/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2333263 |
| CO Springs Hazmat | Original | N | 7/10/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2333261 |
| Energy | Original | D | 6/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2322619 |
| Mechanical | Original | D | 6/17/2026 | TREVORH | TREVORH | Disapproved; Need to turn off the ceiling grid layer and remove RTU's from the floor plan for clarity * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2322618 |
| Electrical | Original | D | 6/17/2026 | CONNERM | CONNERM | Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC."
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Controlled receptacles must be shown on the plan per C405.11
Provide UL listings for Sauna Heaters, Stand Up Tanning Beds, and Hydo-massage chairs
Fault current information (SCCR, AIC, SCA) at all of the following locations. 4. All new air conditioning and refrigeration equipment
All new and existing electrical devices must comply with ANSI 117.1 section 308 reach range
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2322477 |
| Plumbing | Original | D | 6/17/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping and condensate piping related items shall be on the mechanical plans.Remove ALL references to gas piping and condensate piping from the plumbing plans. Recalculate wsfu using table E103.3(2) load values. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2322464 |
| Electronic Plan | Original | / | 6/17/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2322413 |
| CO Springs DRE | Original | D | 6/17/2026 | SSADLER | SSADLER | Contact Charla at charla.hudspeth@coloradosprings.gov to discuss possible fees for the occupancy change.
Approved for a commercial interior remodel and change of occupancy. Plans are approved once fees are collected. No changes to parking, footprint, or landscaping are proposed with this permit. | | CO Springs DRE | 2322392 |
| Electronic Plan | Original | / | 6/17/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2322374 |
| Zoning/Planning | Original | / | 6/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2322207 |
| CSU Water | Original | N | 6/16/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2322162 |
| CSU Waste Water | Original | N | 6/16/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2322160 |
| Construction | Original | D | 6/16/2026 | JUSTINL | JUSTINL | See architectural, structural and code study form for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2322135 |
| Energy | Original | / | 6/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2321787 |
| Electronic Plan | Original | / | 6/15/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2320946 |
| Enumeration | Original | D | 5/26/2026 | AMY | AMY | Code Study form: The Legal Description & Tax Schedule number is required to be filled in on the Code Study form. This information can be found on the El Paso County Assessor’s database when typing in the address of the lot. The Tax schedule number can be found above the address on this website. https://property.spatialest.com/co/elpaso/#/
On page A000.0 the separation of space for this tenant space based on the square footage is incorrect. Correct the separation line so that a proposed new addresses can assigned to the vacant space beside Crunch Fitness. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2311741 |
| Electronic Plan | Original | / | 5/26/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2311678 |
| | Original | / | 5/22/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/22/2026 for plan submitted 05/22/2026. Submit Date updated to now. Plan now open for review. | | | 2311147 |
| Energy | Original | / | 5/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2311093 |
| Floodplain | Original | N | 5/22/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6322214035) | | Floodplain | 2311092 |