| CO Springs DRE | Original | A | 8/13/2026 | SSADLER | SSADLER | Proposed plans are consistent with the approved modified development plan. Due to policy changes, assurances for all private improvements are now due at the time of C/O | | CO Springs DRE | 2347488 |
| City Engr | Original | A | 8/13/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2347284 |
| Energy | Original | D | 8/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346896 |
| Mechanical | Original | D | 8/12/2026 | TREVORH | TREVORH | Disapproved; Need to show condensate drain line routing on plans for AC 1.01 and CRAC 1.01 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2346895 |
| Zoning/Planning | Original | / | 8/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2346829 |
| Electrical | Original | D | 8/12/2026 | DANIELG | DANIELG | Show feeder OCPD's on the one-line.
Show size of the GEC on the one-line.
Patient care areas must show compliance with 517.13 NEC
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2346679 |
| Construction | Original | D | 8/12/2026 | DOUGC | DOUGC | Rated Construction * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2346661 |
| Submittal 2 | Original | / | 8/11/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2346334 |
| CO Springs DRE | Original | D | 8/10/2026 | CHUDSPETH | CHUDSPETH | Plans have been denied until planner review is complete. All CDI fees were paid on 8/10/2026 | | CO Springs DRE | 2345642 |
| CO Springs Fire | Original | D | 7/14/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2334121 |
| CO Springs Hazmat | Original | D | 7/14/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Hazmat | 2334119 |
| Energy | Original | D | 7/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2333830 |
| Mechanical | Original | D | 7/13/2026 | TREVORH | TREVORH | Disapproved; Remove colored wall rating from plan as PPRBD will Need to use their own for identifying wall ratings * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2333829 |
| Electronic Plan | Original | / | 7/13/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2333771 |
| CO Springs DRE | Original | D | 6/29/2026 | SSADLER | SSADLER | Upload the approved and stamped modified development plan. | | CO Springs DRE | 2328017 |
| Electrical | Original | D | 6/25/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2326586 |
| Electronic Plan | Original | / | 6/25/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2326541 |
| Zoning/Planning | Original | / | 6/24/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2326371 |
| Gas/Elec. Utils | Original | A | 6/24/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 2326294 |
| CSU Water | Original | N | 6/24/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2326293 |
| CSU Waste Water | Original | N | 6/24/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2326292 |
| Plumbing | Original | A | 6/24/2026 | SHANEN | SHANEN | | | Plumbing | 2326267 |
| City Engr | Original | D | 6/24/2026 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan modification in the electronic building permit set. | | City Engr | 2326247 |
| Construction | Original | D | 6/24/2026 | DOUGC | DOUGC | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2326153 |
| Electronic Plan | Original | / | 6/19/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2324341 |
| Enumeration | Original | N | 6/19/2026 | BRENT | BRENT | | | Enumeration | 2324036 |
| Electronic Plan | Original | / | 6/19/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2324032 |
| | Original | / | 6/18/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/18/2026 for plan submitted 06/03/2026. Submit Date updated to now. Plan now open for review. | | | 2323459 |
| Energy | Original | / | 6/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2315790 |
| Floodplain | Original | N | 6/3/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6408423013) | | Floodplain | 2315789 |