1420 AUSTIN BLUFFS PKWY, COLORADO SPRINGS, CO 80918
Parcel Info
6329100046
Truss P/SF
30 (Elevation: 6,376 Feet)
Project
NEW ELEVATOR - UCCS ENGINEERING BUILDING (
437
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
COLORADO SPRINGS FIRE DIST
Submit Date
Approval Date
Location
Resubmittal
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 3
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Elevators
/
0
X
Elevators
Energy
N
G
Energy
Floodplain
N
0
W
Floodplain
Log Entries: 7
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
Submittal 2
Original
/
8/10/2026
NICOLASV
NICOLASV
Submittal #2
Submittal 2
2345731
Elevators
Original
D
7/7/2026
ROBERTV
ROBERTV
This review pertains to the installation of a new elevator in the UCCS Engineering Building, identified as Elevator #2
1) Remove sheets in Elevator Shop Drawings for Elevator #1
2) Need to provide engineered Plumbing drawings showing new required sump pump for Elevator #2, piping discharge detail to indirect sanitary, pump specifications showing a minimum of 50 GPM at discharge
3) Need to provide engineered Mechanical drawings showing new required independent source of ventilation or HVAC serving the top of shaft elevator Machinery / Control Space. See link to PPRBD's requirement for our AHJ, Section 7: https://www.pprbd.org/File/ByAlias/policiesforconveyances
4) Also see sheets: A-101B, A-102B, A-460, EL101B, EP101B, EL102B, E602.
Re-Review All
RBD Note: Shop Drawings provided for (1) Kone Machine Room-Less Traction Elevator, 3500 lbs / 150 fpm, connected to Generator, A17.1 - 2019, 2023 RBC
.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Elevators
2331257
Electronic Plan
Original
/
6/24/2026
SHELLEY
SHELLEY
In Current Review by SHELLEY
Electronic Plan
2326483
Floodplain
Original
N
6/22/2026
KEITH
KEITH
Floodplain
2324989
Original
/
6/22/2026
SYSTEM
SYSTEM
Plan Review fees paid 06/22/2026 for plan submitted 06/15/2026. Submit Date updated to now. Plan now open for review.
2324855
Energy
Original
N
6/15/2026
SYSTEM
SYSTEM
Energy Department review not required under 2023 PPRBC when IECC is N/A
Energy
2321411
Floodplain
Original
/
6/15/2026
RBD GIS
RBD GIS
Autogenerated Review: Floodplain status unknown. (Parcel: 6329100046)