| CO Springs Fire | Original | D | 8/11/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2346228 |
| CO Springs Hazmat | Original | D | 8/11/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2346226 |
| CO Springs DRE | Original | D | 7/30/2026 | KDODGE | KDODGE | only item # 1 from DRE disapproval 7/2/26 has been addressed. ALL OTHER ITEMS still need to be corrected/provided. | | CO Springs DRE | 2340952 |
| Mechanical | Original | D | 7/28/2026 | DALEH | DALEH | See building plan review comments Adjust mechanical as needed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2339790 |
| Electrical | Original | D | 7/27/2026 | CONNERM | CONNERM | Clearly indicate compliance with 240.24(B) NEC. Okay to show on Architectural plans, electrical plans not required * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2339402 |
| Zoning/Planning | Original | / | 7/27/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2339325 |
| Plumbing | Original | D | 7/27/2026 | SHANEN | SHANEN | Construction approved occupant load must be provided on the plan label to verify compliance with section 403.1. Provide an occupant load to fixture count analysis on the architectural plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2339301 |
| Electronic Plan | Original | / | 7/27/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2339259 |
| Construction | Original | D | 7/27/2026 | JUSTINL | JUSTINL | See code study form and architectural plans for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2339247 |
| Energy | Original | N | 7/27/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2339246 |
| Electronic Plan | Original | / | 7/24/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2339149 |
| Enumeration | Original | A | 7/24/2026 | BECKYA | BECKYA | Create executive suites - no remodel work proposed. 1 plan 4 permits. | | Enumeration | 2338766 |
| | Original | / | 7/23/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2338619 |
| | Original | / | 7/23/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2338616 |
| Submittal 4 | Original | / | 7/23/2026 | MELISSAF | MELISSAF | Submittal #4 | | Submittal 4 | 2338615 |
| Plan Coordinator (Main) | Original | D | 7/22/2026 | BECKYA | BECKYA | Disapprove all remaining departments to allow plan to be resubmitted - remodel work is still being proposed. In order to create suites separate plans will need to be submitted.
Please see the Executive Suite Policy attached to this plan under "Reviewer Comments"
We highly suggest making an appointment to discuss a path forward. Please schedule an in-person review, link to make an appointment on our website, https://www.pprbd.org/Home/BookAppt * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2337902 |
| Electronic Plan | Original | / | 7/22/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2337896 |
| | Original | / | 7/22/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2337832 |
| | Original | / | 7/22/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2337830 |
| Submittal 3 | Original | / | 7/22/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2337829 |
| CO Springs Hazmat | Original | D | 7/22/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Hazmat | 2337620 |
| CO Springs Fire | Original | D | 7/22/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2337619 |
| Energy | Original | D | 7/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2335052 |
| Plumbing | Original | D | 7/16/2026 | SHANEN | SHANEN | Construction review comments must be addressed to verify compliance with section 403.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2335051 |
| Mechanical | Original | D | 7/7/2026 | DALEH | DALEH | See building plan review comments Adjust mechanical as needed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2331186 |
| CO Springs DRE | Original | D | 7/2/2026 | KDODGE | KDODGE | Please provide: 1) Suite numbers on code study and arch plans do not match, please correct. 2)Upload MJ license showing all licenses MMS, RMS, Cultivation, MIP and/or correct Cody Study IF some licenses listed on study are in error. 3) Label each room on plans. 4) Contact City Clerk if expanding into suites that were not included in last marijuana license modification. 5) CDI fees yet to be determined by Planner | | CO Springs DRE | 2330161 |
| Electrical | Original | D | 6/30/2026 | CONNERM | CONNERM | Electrical okay. Must address enumerations and construction comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2328889 |
| Electronic Plan | Original | / | 6/30/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2328869 |
| CSU Water | Original | N | 6/30/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2328862 |
| CSU Waste Water | Original | N | 6/30/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2328860 |
| Zoning/Planning | Original | / | 6/30/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2328823 |
| Construction | Original | D | 6/30/2026 | JUSTINL | JUSTINL | Remodel work is taking place in all units and creating new suites. This requires that each suite be issued a new certificate of occupancy and would require separate plan and permit for each space to create new suites with remodel. No review performed as it appears that this plan and code study is for the building and not for individual suites.
All departments left on plans to allow for reviewers to make comments as to what may or may not be required by for each discipline with an interior remodel to create new suite. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2328819 |
| Electronic Plan | Original | / | 6/30/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2328749 |
| Enumeration | Original | D | 6/22/2026 | BECKYA | BECKYA | Since remodel work is included in the scope to create suites, a separate plan submittal is required for each space being modified.
Per our Executive Suite policy (see page 2, B (continued) #2.), the work in these spaces will need to be submitted separately. Infilling a wall opening is still considered remodel work. These four spaces will need to be submitted individually as Interior Remodels to Create New Suite. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2324475 |
| Electronic Plan | Original | / | 6/18/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2323160 |
| Electronic Plan | Original | / | 6/18/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2323158 |
| Submittal 2 | Original | / | 6/18/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2323101 |
| Plan Coordinator (Main) | Original | D | 6/16/2026 | BECKYA | BECKYA | Disapprove all remaining departments to allow plan to be resubmitted -
Since remodel work is included in the scope to create suites, a separate plan submittal is required for each space being modified. Additionally, when submitting plans for each suite the suite numbering will need to be 100, 110, 120, 130 & 140. Be sure to submit under the correct suite number and show suite numbering on the floor plan. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2321891 |
| | Original | / | 6/16/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/16/2026 for plan submitted 06/16/2026. Submit Date updated to now. Plan now open for review. | | | 2321817 |
| Energy | Original | / | 6/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2321807 |
| Floodplain | Original | N | 6/16/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6409101002) | | Floodplain | 2321806 |