| CO Springs DRE | Original | D | 8/5/2026 | SSADLER | SSADLER | On the site plan, show the location of the proposed repairs. | | CO Springs DRE | 2343627 |
| Energy | Original | D | 8/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2342531 |
| Mechanical | Original | D | 8/3/2026 | TREVORH | TREVORH | Disapproved; Gas piping plan is missing from this Mechanical submittal package, need to include routing, material, pipe size,BTU's and what table was used out of the 2021 IFGC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2342530 |
| CSU Contract Admin. | Original | D | 8/3/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal/approval of Commercial Water Meter Sizing Form and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111. JMD | jdemello | CSU Contract Admin. | 2342322 |
| CSU Waste Water | Original | D | 8/3/2026 | CSUREVIEW | CSUREVIEW | Please show the location of the existing sand oil interceptor connection and proposed domestic connection to existing wastewater service. Verify no change to wastewater service outside of the building. PSD | PDosch | CSU Waste Water | 2342149 |
| CSU Water | Original | D | 8/3/2026 | CSUREVIEW | CSUREVIEW | Incomplete Plumbing Plan provided, additional comments may be provided with the next submittal. Please clearly show and label existing and proposed domestic service lines and existing meter and backflow. Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.*** PSD | PDosch | CSU Water | 2342138 |
| Plumbing | Original | D | 8/3/2026 | SHANEN | SHANEN | Construction review comments must be addressed. All gas piping and condensate piping related items shall be on the mechanical plans. Remove ALL references to gas piping and condensate piping from the plumbing plans. ST-5 is for residential use only per manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2341977 |
| Electrical | Original | D | 8/3/2026 | DANIELG | DANIELG | Comply with 250.122 NEC.
Comply with 250.102(C)(1) NEC.
Major or minor repair garage?
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2341951 |
| Electronic Plan | Original | / | 8/3/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2341931 |
| Zoning/Planning | Original | / | 8/3/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2341907 |
| Construction | Original | D | 8/3/2026 | JUSTINL | JUSTINL | No review performed. See Enumerations comment. Multiple tenant building with different suite numbers. No suite number provided. Unable to identify where the fire damage repair is taking place in the building. No architectural plan provided. See handout on website for commercial plan review requirements. https://www.pprbd.org/File/ByAlias/CommPlanReview https://www.pprbd.org/File/ByAlias/ComRemodel * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2341885 |
| Electronic Plan | Original | / | 7/31/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2341839 |
| Enumeration | Original | D | 7/31/2026 | BRENT | BRENT | This building has historically been a multi-tenant building. Show all tenant spaces with addressing and the area of work highlighted. Show the suite number for this building on the code study form and on all plan pages where the address appears. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2341735 |
| Electronic Plan | Original | / | 7/31/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2341726 |
| | Original | / | 7/31/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/31/2026 for plan submitted 06/18/2026. Submit Date updated to now. Plan now open for review. | | | 2341691 |
| Energy | Original | / | 6/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2323169 |
| Floodplain | Original | N | 6/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6434113011) | | Floodplain | 2323168 |