| Triview Water | Original | A | 8/10/2026 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Water | 2345381 |
| EPC Health Dept | Original | A | 8/3/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AB | abrannon | EPC Health Dept | 2342459 |
| Mechanical | Original | D | 7/30/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2340863 |
| Monument Hazmat | Original | N | 7/29/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Monument Hazmat | 2340727 |
| Monument Fire | Original | A | 7/29/2026 | MONUMENTFIRE | MONUMENTFIRE | This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines.Field Verification Approved plans are subject to field verification. Installations not in accordance with approved plans or applicable codes may require correction. | SBenson9 | Monument Fire | 2340725 |
| Plumbing | Original | D | 7/29/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Slope shall comply with section 704.1. All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2340628 |
| Electrical | Original | D | 7/29/2026 | CONNERM | CONNERM | Provide fault current info (AIC and SCR) for new air condition equipment * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2340626 |
| Electronic Plan | Original | / | 7/29/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2340614 |
| Construction | Original | A | 7/29/2026 | DOUGC | DOUGC | | | Construction | 2340600 |
| Enumeration | Original | N | 7/29/2026 | AMY | AMY | The legal description was added for you. Please note where to find it and fill this in, in the future. | | Enumeration | 2340594 |
| Electronic Plan | Original | / | 7/29/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2340590 |
| Submittal 2 | Original | / | 7/29/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2340552 |
| Plumbing | Original | D | 7/16/2026 | SHANEN | SHANEN | B occupancy with an occupant load of 39 must comply with section 403.1. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Slope shall comply with section 704.1. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview Provide a piping materials schedule. 3/4" is undersized to serve downstream fixtures. Water closet must be supplied by a 1" water line per fixture schedule. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2335313 |
| Monument Hazmat | Original | N | 7/14/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Monument Hazmat | 2333981 |
| Monument Fire | Original | A | 7/14/2026 | MONUMENTFIRE | MONUMENTFIRE | This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines.Deferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation.Field Verification Approved plans are subject to field verification. Installations not in accordance with approved plans or applicable codes may require correction.Inspection Scheduling All inspections shall be requested a minimum of 48 hours in advance through Monument Fire. Contact permits@monumentfire.org Approval by Monument Fire does not relieve the applicant from compliance with all other applicable codes, ordinances, and requirements from other agencies having jurisdiction. | SBenson9 | Monument Fire | 2333980 |
| Mechanical | Original | D | 7/8/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2331644 |
| Monument Zoning | Original | N | 7/7/2026 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Zoning | 2331252 |
| EPC Health Dept | Original | D | 7/7/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2331093 |
| Electrical | Original | D | 7/1/2026 | CONNERM | CONNERM | Remove ground from service conductors
Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2329671 |
| Electronic Plan | Original | / | 7/1/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2329642 |
| Construction | Original | D | 7/1/2026 | DOUGC | DOUGC | CSF // Occ Load // Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2329633 |
| Energy | Original | N | 7/1/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2329632 |
| Electronic Plan | Original | / | 7/1/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2329551 |
| Triview Water | Original | D | 6/29/2026 | TRIVIEWMETRO | TRIVIEWMETRO | Historical documents for this unit indicate a 2” DCW service entering the building, but meter size and unit tap size are not clearly specified. A ¾” meter and HDPE service is likely too small for the anticipated flow. Please check existing service line and meter size and confirm that it is sufficient for the proposed usage. | rnortonTMD | Triview Water | 2328114 |
| Triview Waste Water | Original | A | 6/29/2026 | TRIVIEWMETRO | TRIVIEWMETRO | Approved variance for proposed 50gpm grease trap per Jim | rnortonTMD | Triview Waste Water | 2328111 |
| Enumeration | Original | D | 6/22/2026 | AMY | AMY | The Legal Description on the Code Study form needs to be filled in. This information can be found on the El Paso County Assessor’s website. This is the description of the lot and subdivision. Add the suite number/letters to the site map page A000. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2324584 |
| Electronic Plan | Original | / | 6/22/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2324565 |
| | Original | / | 6/19/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/19/2026 for plan submitted 06/19/2026. Submit Date updated to now. Plan now open for review. | | | 2324054 |
| Waste Water Div | Original | / | 6/19/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2323882 |
| Water Division | Original | / | 6/19/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2323881 |
| Energy | Original | / | 6/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2323880 |
| Floodplain | Original | N | 6/19/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7126005003) | | Floodplain | 2323879 |