| CSU Contract Admin. | Original | D | 9/2/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and possible payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2355864 |
| Energy | Original | D | 9/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2355456 |
| Mechanical | Original | A | 9/2/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2355455 |
| Electrical | Original | D | 9/2/2026 | BERTHA | BERTHA | Comply with previous review comment - on the one-line - Provide all conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Comply with previous review comment - Provide SCCR / AIC for all required equipment in the Fault Calculation table - Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Comply with previous review comment - provide a note indicating the exemption for the following - Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2355300 |
| CO Springs DRE | Original | A | 9/2/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2355277 |
| Electronic Plan | Original | / | 9/2/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2355200 |
| CSU Waste Water | Original | D | 9/1/2026 | CSUREVIEW | CSUREVIEW | See previous comments.
Datum #4 is not sufficient. A Utility Service Plan is required for the exterior sanitary connection shown on P 110. Contact UDS at 719-668-8261 .MDA | malcuran | CSU Waste Water | 2355129 |
| CSU Water | Original | D | 9/1/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Upload approved CWMSF. MDA | malcuran | CSU Water | 2355125 |
| Zoning/Planning | Original | / | 9/1/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2355119 |
| Plumbing | Original | D | 9/1/2026 | SHANEN | SHANEN | The following general note must be included on the plumbing plans: A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC. Per enumeration, the address number is 3630. Provide correct address on all drawings. Incorrect address provided on the required CSU grease interceptor variance letter. CSU comments regarding the building drain connection must be addressed. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Remove all references to gas piping from the plumbing plans. Scheduled grease interceptor does not match the CSU variance letter. Water heater detail must show compliance with 2021 IECC section 404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2355081 |
| Construction | Original | D | 9/1/2026 | MATTHEWA | MATTHEWA | Accessory occupancies on code study form. // Life safety plan // Accessible elements // Door clarification * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2355011 |
| Electronic Plan | Original | / | 9/1/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2354829 |
| Enumeration | Original | A | 9/1/2026 | BECKYA | BECKYA | | | Enumeration | 2354779 |
| Submittal 2 | Original | / | 9/1/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2354588 |
| CO Springs Fire | Original | D | 8/12/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2346943 |
| CO Springs Hazmat | Original | N | 8/12/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2346942 |
| CO Springs DRE | Original | A | 7/31/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No fees due for use change. Use allowed per the dp | | CO Springs DRE | 2341588 |
| CSU Contract Admin. | Original | D | 7/29/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and potential payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2340599 |
| Energy | Original | D | 7/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2340158 |
| Electrical | Original | D | 7/28/2026 | BERTHA | BERTHA | Provide all conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide overcurrent protection for MCB and feeders on the one-line
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Pending approval in Enumeration - see Enumeration review comments.
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior), and C405.2.8 (Parking Garages), where applicable.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2340157 |
| Mechanical | Original | D | 7/28/2026 | TREVORH | TREVORH | Disapproved; Need to remove all Gas related References from the plumbing submittal and show only in the mechanical submission * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2339925 |
| Zoning/Planning | Original | / | 7/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2339901 |
| Electronic Plan | Original | / | 7/28/2026 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2339830 |
| Plumbing | Original | D | 7/28/2026 | SHANEN | SHANEN | Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. Show sizing at point of connection to verify compliance with section 704.2. Horizontal dry vents are not in compliance with section 905.4. Lavatories must show compliance with 2021 IECC section C404.5.1. Controls and hand showers shall comply with ICC A117.1-2017 section 608.4. Provide isometric drawings showing sizing for each branch and section of the water distribution system. Provide isometric drawings showing sizing for each branch and section of the DWV system. Provide required CSU variance letter for the indoor grease interceptor. Contact Robert Bowren at 719-668-1735 or fog@csu.org.CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Water heater detail must show compliance with 2021 IECC section 404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2339821 |
| CSU Waste Water | Original | D | 7/28/2026 | CSUREVIEW | CSUREVIEW | Possible utility service plan required due to 6-inch sanitary service line outside of building to the south (sheet P110). If existing sanitary line then label as such.MDA | malcuran | CSU Waste Water | 2339789 |
| CSU Water | Original | D | 7/28/2026 | CSUREVIEW | CSUREVIEW | Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.***MDA | malcuran | CSU Water | 2339784 |
| Electronic Plan | Original | / | 7/28/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2339780 |
| Construction | Original | D | 7/28/2026 | MATTHEWA | MATTHEWA | Code study form // Doors and hardware // Accessibility // Wall types * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2339777 |
| Electronic Plan | Original | / | 7/24/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2338750 |
| Enumeration | Original | D | 7/7/2026 | BECKYA | BECKYA | Provide secondary addressing and current separation of spaces on the site plan. Update all plan pages to show the correct address 3630 Austin Bluffs Parkway 190 no "C" * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2331233 |
| Electronic Plan | Original | / | 7/7/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2331226 |
| | Original | / | 7/6/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/06/2026 for plan submitted 07/06/2026. Submit Date updated to now. Plan now open for review. | | | 2330855 |
| Energy | Original | / | 7/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2330692 |
| Floodplain | Original | N | 7/6/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6327121018) | | Floodplain | 2330691 |