| Electrical | Original | A | 8/26/2026 | CONNERM | CONNERM | | | Electrical | 2352273 |
| Electronic Plan | Original | / | 8/26/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2352256 |
| | Original | / | 8/26/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2352248 |
| | Original | / | 8/26/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2352238 |
| Submittal 4 | Original | / | 8/26/2026 | MELISSAF | MELISSAF | Submittal #4 | | Submittal 4 | 2352237 |
| CO Springs DRE | Original | A | 8/26/2026 | SSADLER | SSADLER | Previous approval comments still apply. | | CO Springs DRE | 2352212 |
| Electrical | Original | D | 8/21/2026 | CONNERM | CONNERM | Provide fault current info (SCCR, AIC, SCA) for all new/refed/relocated air conditioning equipment
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2350953 |
| Zoning/Planning | Original | / | 8/21/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2350948 |
| Electronic Plan | Original | / | 8/21/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2350925 |
| Construction | Original | A | 8/21/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2350921 |
| | Original | / | 8/21/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2350762 |
| | Original | / | 8/21/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2350761 |
| Submittal 3 | Original | / | 8/21/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2350760 |
| Mechanical | Original | A | 8/17/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2348301 |
| CO Springs DRE | Original | A | 8/17/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2348270 |
| Electronic Plan | Original | / | 8/14/2026 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2348164 |
| Electronic Plan | Original | / | 8/14/2026 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 2348163 |
| Zoning/Planning | Original | / | 8/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2347785 |
| Electrical | Original | D | 8/14/2026 | CONNERM | CONNERM | Information must be verified at time of review by licensed engineer. Provide fault current info (SCCR, AIC, SCA) for all new/refed panelboards, AC equipment, and transfer equipment.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2347771 |
| Electronic Plan | Original | / | 8/14/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2347734 |
| Construction | Original | D | 8/14/2026 | BPHILLIPS | BPHILLIPS | Life safety plan, accessibility clearance. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2347733 |
| Electronic Plan | Original | / | 8/14/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2347708 |
| Submittal 2 | Original | / | 8/14/2026 | TREYW | TREYW | Submittal #2 | | Submittal 2 | 2347697 |
| CO Springs Fire | Original | A | 8/12/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2346516 |
| CO Springs Hazmat | Original | N | 8/12/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2346515 |
| Mechanical | Original | D | 8/10/2026 | TREVORH | TREVORH | Disapproved; Need to provide the MECHANICALComCheck * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2345443 |
| Electronic Plan | Original | / | 8/4/2026 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2343191 |
| CSU Contract Admin. | Original | N | 7/29/2026 | CSUAPPSPRM | CSUAPPSPRM | No additional fees required for this plan set.
AMS | ASweet | CSU Contract Admin. | 2340440 |
| Stormwater | Original | N | 7/29/2026 | GHUNTLEY | GHUNTLEY | No stormwater scope of work, | | Stormwater | 2340389 |
| CSU Water | Original | N | 7/28/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2340219 |
| CSU Waste Water | Original | N | 7/28/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2340218 |
| Gas/Elec. Utils | Original | A | 7/28/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 2340216 |
| Electrical | Original | D | 7/28/2026 | CONNERM | CONNERM | Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2340170 |
| City Engr | Original | N | 7/28/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2340150 |
| Electronic Plan | Original | / | 7/28/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2340113 |
| Plumbing | Original | N | 7/28/2026 | SHANEN | SHANEN | | | Plumbing | 2340098 |
| CO Springs DRE | Original | A | 7/28/2026 | KDODGE | KDODGE | interior remodel, no change in use. Renovation of existing interior offices, workroom, conference room. | | CO Springs DRE | 2340083 |
| Construction | Original | D | 7/28/2026 | BPHILLIPS | BPHILLIPS | Occupant load calcs, vestibule accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2340055 |
| Energy | Original | N | 7/28/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2339989 |
| Electronic Plan | Original | / | 7/28/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2339800 |
| Enumeration | Original | N | 7/8/2026 | AMY | AMY | | | Enumeration | 2331754 |
| Electronic Plan | Original | / | 7/8/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2331740 |
| | Original | / | 7/8/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/08/2026 for plan submitted 07/07/2026. Submit Date updated to now. Plan now open for review. | | | 2331543 |
| Energy | Original | / | 7/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2331422 |
| Floodplain | Original | N | 7/7/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7323106007) | | Floodplain | 2331421 |