| Energy | Original | D | 8/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2347577 |
| Mechanical | Original | D | 8/13/2026 | TREVORH | TREVORH | Disapproved; Architectural plan set is showing this space east of column line 1 as a driveway how will condenser be protected? Also outside air intake needs to be 10' from a driveway * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2347576 |
| Plumbing | Original | D | 8/11/2026 | SHANEN | SHANEN | Interior finish requires compliance with section 403.1 (drinking fountain required).Schedule the required drinking fountain. Show piping for and location of required drinking fountain. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2345828 |
| Electrical | Original | D | 8/10/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11 OR have approved AM&M at the time of review
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Indicate compliance with 240.24 (B) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2345179 |
| Electronic Plan | Original | / | 8/10/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2345148 |
| Elevators | Original | N | 8/7/2026 | JOHN | JOHN | no elevator in scope | | Elevators | 2345108 |
| County Zoning | Original | N | 8/7/2026 | DSDRANGEL | DSDRANGEL | | | County Zoning | 2345025 |
| Zoning/Planning | Original | / | 8/7/2026 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 2345024 |
| EPC Health Dept | Original | N | 8/7/2026 | HEALTHDEPT | HEALTHDEPT | Office warehouse not applicable. AB | abrannon | EPC Health Dept | 2345015 |
| Gas/Elec. Utils | Original | D | 8/7/2026 | CSUREVIEW | CSUREVIEW | Contact Springs Utilities Field Engineers to deign the gas and electric service, meter locations and transformers. Gas: Santiago Tijerina 719-668-3572 Electric: Mike Garcia 719-668-7887
reviewed by: mjg | mgackle | Gas/Elec. Utils | 2345001 |
| CSU Contract Admin. | Original | N | 8/7/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due this plan set. BS | bschifferstein | CSU Contract Admin. | 2344976 |
| Construction | Original | D | 8/7/2026 | MATTHEWA | MATTHEWA | Code references // Life safety plan // Clear floor space // Drinking fountains * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2344947 |
| Energy | Original | / | 8/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2344545 |
| Electronic Plan | Original | / | 8/6/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2344326 |
| Enumeration | Original | D | 8/5/2026 | BECKYA | BECKYA | Update all plans to show one suite number. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2343674 |
| Electronic Plan | Original | / | 8/5/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2343659 |
| | Original | / | 8/5/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/05/2026 for plan submitted 08/05/2026. Submit Date updated to now. Plan now open for review. | | | 2343461 |
| Stormwater | Original | / | 8/5/2026 | SYSTEM | SYSTEM | You will need to contact Stormwater department for approval prior to permit. This department will not review the plan electronically. | | Stormwater | 2343333 |
| Waste Water Div | Original | / | 8/5/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2343334 |
| Water Division | Original | / | 8/5/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2343332 |
| Energy | Original | / | 8/5/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2343331 |
| Floodplain | Original | N | 8/5/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6428301005) | | Floodplain | 2343330 |