| Electrical | Original | A | 10/1/2026 | CONNERM | CONNERM | | | Electrical | 2366259 |
| Electronic Plan | Original | / | 10/1/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2366240 |
| Construction | Original | D | 10/1/2026 | MATTHEWA | MATTHEWA | Life safety plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2366225 |
| Plumbing | Original | A | 10/1/2026 | SHANEN | SHANEN | | | Plumbing | 2365887 |
| Enumeration | Original | A | 10/1/2026 | AMY | AMY | | | Enumeration | 2365721 |
| Electronic Plan | Original | / | 10/1/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2365720 |
| | Original | / | 10/1/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2365716 |
| | Original | / | 9/30/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2365605 |
| Submittal 3 | Original | / | 9/30/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2365604 |
| CO Springs Fire | Original | D | 9/23/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2362655 |
| CO Springs Hazmat | Original | D | 9/23/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2362654 |
| CO Springs DRE | Original | A | 9/16/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2360031 |
| Gas/Elec. Utils | Original | N | 9/15/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CG | cgraves | Gas/Elec. Utils | 2359387 |
| Energy | Original | D | 9/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2359377 |
| Plumbing | Original | D | 9/15/2026 | SHANEN | SHANEN | See clouded sections on additional requirements for 2021 IECC block. Remove all references to gas piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2359376 |
| Mechanical | Original | A | 9/14/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2359158 |
| Electrical | Original | A | 9/14/2026 | CONNERM | CONNERM | | | Electrical | 2359131 |
| Zoning/Planning | Original | / | 9/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2359123 |
| Electronic Plan | Original | / | 9/14/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2359109 |
| Construction | Original | D | 9/14/2026 | MATTHEWA | MATTHEWA | Code study form // Life safety plan // Square footages for occupant load factor * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2359100 |
| Enumeration | Original | A | 9/9/2026 | AMY | AMY | | | Enumeration | 2357364 |
| Electronic Plan | Original | / | 9/9/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2357348 |
| Submittal 2 | Original | / | 9/4/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2356755 |
| CO Springs Fire | Original | D | 8/31/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2354470 |
| CO Springs Hazmat | Original | D | 8/31/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2354469 |
| Energy | Original | D | 8/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2348249 |
| Mechanical | Original | D | 8/17/2026 | TCRIPPEN | TCRIPPEN | Disapproved pending construction * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2348248 |
| CO Springs DRE | Original | A | 8/13/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No exterior changes | | CO Springs DRE | 2347037 |
| Plumbing | Original | D | 8/12/2026 | SHANEN | SHANEN | Occupant load requires a service sink. Show location of and piping for the required service sink. Schedule required service sink. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All condensate piping must be on the mechanical plans. Remove ALL references to condensate piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2346497 |
| City Engr | Original | N | 8/11/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2346342 |
| Gas/Elec. Utils | Original | D | 8/11/2026 | CSUREVIEW | CSUREVIEW | Submit Electric Load Data Form to CSU Field Engineering. Form can be found at: https://www.csu.org/hubfs/Document-Library/ElectricLoadData.pdf?hsLang=en DMM | dmakings | Gas/Elec. Utils | 2346239 |
| Stormwater | Original | N | 8/10/2026 | JDUNCAN | JDUNCAN | No Stormwater scope of work. | | Stormwater | 2345734 |
| CSU Contract Admin. | Original | N | 8/10/2026 | CSUAPPSPRM | CSUAPPSPRM | No additional fees required for this plan set.
AMS | ASweet | CSU Contract Admin. | 2345733 |
| CSU Water | Original | N | 8/10/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2345583 |
| CSU Waste Water | Original | N | 8/10/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2345582 |
| Zoning/Planning | Original | / | 8/10/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2345474 |
| Electrical | Original | D | 8/10/2026 | CONNERM | CONNERM | Show compliance with 517.13
Provide Fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
See one-line * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2345383 |
| Electronic Plan | Original | / | 8/10/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2345372 |
| Construction | Original | D | 8/10/2026 | MATTHEWA | MATTHEWA | Code study form // Life safety plan // Occupant loads // Rated corridors // Use clarification // Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2345362 |
| Electronic Plan | Original | / | 8/10/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2345181 |
| Electronic Plan | Original | / | 8/7/2026 | MATTHEW | MATTHEW | In Current Review by MATTHEW | | Electronic Plan | 2344913 |
| Enumeration | Original | A | 8/6/2026 | AMY | AMY | This area is platted and the updated legal description is showing up in the El Paso County Assessor’s database and should be shown on the Code Study form. This was added for you. Addressing added to sheet A-101 and roadway labeled. | | Enumeration | 2344098 |
| Electronic Plan | Original | / | 8/6/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2344087 |
| | Original | / | 8/6/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/06/2026 for plan submitted 08/06/2026. Submit Date updated to now. Plan now open for review. | | | 2344004 |
| Energy | Original | / | 8/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2343999 |
| Floodplain | Original | N | 8/6/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6207112011) | | Floodplain | 2343998 |