| Triview Waste Water | Original | A | 9/15/2026 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Waste Water | 2359684 |
| Triview Water | Original | A | 9/15/2026 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Since the plumbing plans specify installation of a new 2” backflow preventer, please provide Triview standard detail for water service entry backflow preventer, as given on civil plans for core and shell. | rnortonTMD | Triview Water | 2359683 |
| Energy | Original | D | 9/4/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2356672 |
| Mechanical | Original | D | 9/4/2026 | DALEH | DALEH | Provide a complete gas piping plan Provide a complete condensate routing and size on plans See plans for complete comments
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2356671 |
| Monument Hazmat | Original | N | 9/1/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Monument Hazmat | 2354749 |
| Monument Fire | Original | A | 9/1/2026 | MONUMENTFIRE | MONUMENTFIRE | This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines.
Deferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation.
WRC permits are required for this permit. Please apply at www.monumentfire.org/permits
This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines. | SBenson9 | Monument Fire | 2354748 |
| Plumbing | Original | D | 8/28/2026 | SHANEN | SHANEN | All gas piping and condensate piping related items shall be on the mechanical plans. ST-5 is for residential use only per manufacturer. Remove all references to gas piping and condensate piping from the plumbing plans. The following general note must be included on the plumbing plans: A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC. Lavatories must show compliance with 2021 IECC section C404.5.1. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Water heater detail must show compliance with 2021 IECC section 404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2353662 |
| Electrical | Original | D | 8/28/2026 | DANIELG | DANIELG | Fault current information (SCCR, AIC, SCA) at all of the following locations. See FAULT CURRENT
1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide series rated combinations from the manufacturer.
Controlled receptacles must be shown on the plan per C405.11
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Comply with CE301.1 MERSRC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2353643 |
| Electronic Plan | Original | / | 8/28/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2353630 |
| Elevators | Original | N | 8/28/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2353620 |
| Construction | Original | D | 8/27/2026 | BPHILLIPS | BPHILLIPS | Code study form, life safety plan, accessibility, IECC energy options. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2353399 |
| Electronic Plan | Original | / | 8/27/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2352864 |
| Enumeration | Original | D | 8/26/2026 | AMY | AMY | Code Study Form: A new Parcel number and Legal description of the property has been assigned since the area has platted. Add the platted Legal description and parcel number. Site plan: A site plan of the area is required for Enumerations purposes. Include this with the A sheets. Floor plan: Building showing the separation of space per tenants will all suite numbers included from the Core & Shell plan. Cloud the area of work. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2352776 |
| Electronic Plan | Original | / | 8/26/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2352770 |
| Submittal 2 | Original | / | 8/26/2026 | TREYW | TREYW | Submittal #2 | | Submittal 2 | 2352661 |
| Triview Water | Original | D | 8/25/2026 | TRIVIEWMETRO | TRIVIEWMETRO | Disapproved per plan coordinator to allow resubmittal | rnortonTMD | Triview Water | 2351850 |
| Triview Waste Water | Original | D | 8/25/2026 | TRIVIEWMETRO | TRIVIEWMETRO | Disapproved per plan coordinator to allow resubmittal | rnortonTMD | Triview Waste Water | 2351849 |
| Plan Coordinator (Main) | Original | D | 8/18/2026 | AMY | AMY | Disapprove all remaining departments to allow plan to be resubmitted * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2349243 |
| Enumeration | Original | D | 8/18/2026 | AMY | AMY | Until the Core and Shell Plan has been permitted an interior finish plan cannot be submitted. Please wait until this permit is pulled to resubmit. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2349242 |
| Electronic Plan | Original | / | 8/18/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2349106 |
| | Original | / | 8/18/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/18/2026 for plan submitted 08/18/2026. Submit Date updated to now. Plan now open for review. | | | 2348989 |
| Water Division | Original | / | 8/18/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2348955 |
| Waste Water Div | Original | / | 8/18/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2348956 |
| Energy | Original | / | 8/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2348954 |
| Floodplain | Original | N | 8/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7126005025) | | Floodplain | 2348953 |