| Energy | Original | D | 10/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2369792 |
| Mechanical | Original | D | 10/12/2026 | TREVORH | TREVORH | Disapproved;This Document needs to be signed and stamped by a Colorado design professional ,hood sheets need to be provided * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2369791 |
| | Original | / | 10/8/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2368940 |
| | Original | / | 10/8/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2368920 |
| Submittal 3 | Original | / | 10/8/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2368919 |
| Manitou Zoning | Original | A | 10/2/2026 | MSZONING | MSZONING | Minor Site Plan approved, pending review of drainage letter submitted 10/2/26 - CR | CStromberg | Manitou Zoning | 2366662 |
| Construction | Original | A | 9/28/2026 | DOUGC | DOUGC | | | Construction | 2364528 |
| Energy | Original | D | 9/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2364209 |
| Mechanical | Original | D | 9/28/2026 | TREVORH | TREVORH | Disapproved; Need to see mark ups from the 8-31-26 mechanical review Addressed, currently Disapproval comments have not been addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2364208 |
| Plumbing | Original | A | 9/25/2026 | SHANEN | SHANEN | | | Plumbing | 2363709 |
| Electrical | Original | A | 9/25/2026 | CONNERM | CONNERM | | | Electrical | 2363706 |
| Electronic Plan | Original | / | 9/25/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2363658 |
| Construction | Original | D | 9/25/2026 | DOUGC | DOUGC | Exterior rated wall tags // Fire Barrier // IECC // SQFT Variance * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2363651 |
| Submittal 2 | Original | / | 9/24/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2363489 |
| Manitou Waste Water | Original | A | 9/24/2026 | MSWATER | MSWATER | | bschmittcms | Manitou Waste Water | 2363262 |
| Manitou Zoning | Original | D | 9/24/2026 | MSZONING | MSZONING | Pending engineering comments regarding the driveway curb detail | CStromberg | Manitou Zoning | 2363222 |
| Manitou Water | Original | A | 9/22/2026 | MSWATER | MSWATER | Water System Improvement Fee required for upsizing to 2" tap. | bschmittcms | Manitou Water | 2362288 |
| Manitou Hazmat | Original | A | 9/7/2026 | MSFIRE | MSFIRE | Ok per B Dorris | bdorris | Manitou Hazmat | 2356875 |
| Energy | Original | D | 8/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2354218 |
| Mechanical | Original | D | 8/31/2026 | TREVORH | TREVORH | Disapproved; Need to show condensate drain lines on plans include size, material type and point of disposal on plans. Need to see construction review comments addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2354217 |
| Manitou Fire | Original | A | 8/26/2026 | MSFIRE | MSFIRE | Ok per B Dorris | bdorris | Manitou Fire | 2352288 |
| Electrical | Original | D | 8/25/2026 | CONNERM | CONNERM | Suit bathroom lighting must comply with C405.2.5 IECC
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior)
Verify compliance with CSU LESS 5.04 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2351945 |
| Plumbing | Original | A | 8/25/2026 | SHANEN | SHANEN | | | Plumbing | 2351920 |
| Gas/Elec. Utils | Original | N | 8/25/2026 | CSUREVIEW | CSUREVIEW | | jsnoel | Gas/Elec. Utils | 2351859 |
| Electronic Plan | Original | / | 8/25/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2351853 |
| Construction | Original | D | 8/25/2026 | DOUGC | DOUGC | SQFT // LSP // ACCESSIBILITY // IECC // RATED CONSTRUCTION * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2351799 |
| Electronic Plan | Original | / | 8/21/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2350615 |
| Enumeration | Original | N | 8/19/2026 | BRENT | BRENT | | | Enumeration | 2349744 |
| Electronic Plan | Original | / | 8/19/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2349743 |
| | Original | / | 8/19/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/19/2026 for plan submitted 08/18/2026. Submit Date updated to now. Plan now open for review. | | | 2349703 |
| Energy | Original | / | 8/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2349371 |
| Floodplain | Original | N | 8/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7405309013) | | Floodplain | 2349370 |