| Energy | Original | D | 9/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2356129 |
| Mechanical | Original | D | 9/3/2026 | TREVORH | TREVORH | Disapproved; Need Engineered stamped Mechanical drawings for Review. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2356128 |
| CO Springs DRE | Original | D | 8/28/2026 | CHUDSPETH | CHUDSPETH | Please state if window wells are existing or if you are making them larger. If are making them larger you will need to provide a site-plan. To obtain a site-plan you can email us at dreplanninginfo@coloradosprings.gov | | CO Springs DRE | 2353886 |
| Zoning/Planning | Original | / | 8/27/2026 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2353439 |
| CSU Water | Original | D | 8/27/2026 | CSUREVIEW | CSUREVIEW | Please show existing water and wastewater lines. Please show the location of the proposed connection to the existing. Please clarify that no new water or wastewater service is being proposed outside of the building. PSD | PDosch | CSU Water | 2353352 |
| CSU Waste Water | Original | D | 8/27/2026 | CSUREVIEW | CSUREVIEW | Please show existing water and wastewater lines. Please show the location of the proposed connection to the existing. Please clarify that no new water or wastewater service is being proposed outside of the building. PSD | PDosch | CSU Waste Water | 2353351 |
| Electrical | Original | D | 8/27/2026 | CONNERM | CONNERM | Remove amendments. No longer apply to unamended IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2353334 |
| Electronic Plan | Original | / | 8/27/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2353324 |
| Plumbing | Original | D | 8/27/2026 | SHANEN | SHANEN | CO registered design professional stamp and signature required. Reference 2021 IPC. Provide plumbing plans that comply with PPRBD plumbing plan review requirements. See link:https://www.pprbd.org/File/ByAlias/PlumbingReview * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2353161 |
| Construction | Original | D | 8/27/2026 | MATTHEWA | MATTHEWA | Provide stamped plans by licensed design professional // Provide life safety plan and design criteria // See commercial remodel handout on website for all requirements. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2353110 |
| Electronic Plan | Original | / | 8/27/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2353039 |
| Enumeration | Original | N | 8/27/2026 | AMY | AMY | | | Enumeration | 2352954 |
| Electronic Plan | Original | / | 8/27/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2352829 |
| | Original | / | 8/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/26/2026 for plan submitted 08/26/2026. Submit Date updated to now. Plan now open for review. | | | 2352751 |
| Energy | Original | / | 8/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2352671 |
| Floodplain | Original | N | 8/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7312411025) | | Floodplain | 2352670 |