| Mechanical | Original | D | 9/3/2026 | TREVORH | TREVORH | Disapproved; Need to provide a refrigeration calculation for the mini split system * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2356337 |
| CO Springs DRE | Original | A | 9/1/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to use, landscaping, footprint, or parking. | | CO Springs DRE | 2355008 |
| CSU Water | Original | N | 8/31/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2354309 |
| CSU Waste Water | Original | N | 8/31/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2354308 |
| CSU Waste Water | Original | N | 8/31/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2354307 |
| Electrical | Original | D | 8/31/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11 Or have approved AM&M at time of review
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Show location of all electrical panels * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2354219 |
| Zoning/Planning | Original | / | 8/31/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2354214 |
| Plumbing | Original | A | 8/31/2026 | SHANEN | SHANEN | | | Plumbing | 2354178 |
| Electronic Plan | Original | / | 8/31/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2354172 |
| Construction | Original | D | 8/31/2026 | DOUGC | DOUGC | CSF // LSP * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2354161 |
| Energy | Original | N | 8/31/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2354160 |
| Electronic Plan | Original | / | 8/31/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2354102 |
| Enumeration | Original | D | 8/31/2026 | AMY | AMY | Plan was checked in under suite 200 but all the sheet say suite 220. This seems to be suite 220.
The Legal Description & Tax Schedule number is required to be filled in on the Code Study form. This information can be found on the El Paso County Assessor’s database when typing in the address of the lot. The Tax schedule number can be found above the address on this website. https://property.spatialest.com/co/elpaso/#/ Also, add the suite number and the street suffix is Blvd and not Road -add to the code study form and ComCheck Cert..
The suite numbering for this floor were added for you on sheet G000, if this sheet gets changed out replace the suite numbering. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2354014 |
| Electronic Plan | Original | / | 8/31/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2354001 |
| | Original | / | 8/30/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/30/2026 for plan submitted 08/28/2026. Submit Date updated to now. Plan now open for review. | | | 2353973 |
| Energy | Original | / | 8/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2353535 |
| Floodplain | Original | N | 8/28/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6234406009) | | Floodplain | 2353534 |