| Electrical | Original | A | 10/5/2026 | CONNERM | CONNERM | Must comply with LESS 5.04 | | Electrical | 2366949 |
| Electronic Plan | Original | / | 10/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2366928 |
| Enumeration | Original | A | 10/5/2026 | BECKYA | BECKYA | | | Enumeration | 2366897 |
| | Original | / | 10/5/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2366839 |
| | Original | / | 10/2/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2366704 |
| Submittal 3 | Original | / | 10/2/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2366703 |
| Electrical | Original | D | 10/1/2026 | CONNERM | CONNERM | Show compliance with 240.6 (B) and 240.6 (C)
Provide conductor size, type, and quantity. What size is EGC?
Comply with CSU LESS 5.04.
Comply with 250.24 (C) and 205.24 (E) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2366116 |
| Electrical | Original | D | 9/28/2026 | CONNERM | CONNERM | Show compliance with 240.6 (B) and 240.6 (C)
Provide conductor size, type, and quantity. What size is EGC?
Comply with CSU LESS 5.04.
Comply with 250.24 (C) and 205.24 (E) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2363943 |
| Electronic Plan | Original | / | 9/28/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2363920 |
| Enumeration | Original | A | 9/25/2026 | BECKYA | BECKYA | | | Enumeration | 2363908 |
| Submittal 2 | Original | / | 9/25/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2363822 |
| CO Springs Hazmat | Original | A | 9/15/2026 | CSFIRE | CSFIRE | DFM-C-DC-26-00002 CSFD DFM You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. DFM Plan Review Fee: PAID ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2359287 |
| CO Springs Fire | Original | N | 9/11/2026 | CSFIRE | CSFIRE | No Fire Final
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | Jacob.Watson | CO Springs Fire | 2358414 |
| CO Springs DRE | Original | A | 9/2/2026 | SSADLER | SSADLER | Approved for proposed EV charges. All approval documents on file. | | CO Springs DRE | 2355298 |
| Electrical | Original | D | 9/1/2026 | CONNERM | CONNERM | Provide conduit/conductor size, type CU or AL and quantity beginning at the utility transformer
Provide fault current information (SCCR, AIC, SCA) at new panelboard
Clarify MCB size * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2354924 |
| Zoning/Planning | Original | / | 9/1/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2354917 |
| Electronic Plan | Original | / | 9/1/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2354892 |
| Gas/Elec. Utils | Original | A | 9/1/2026 | CSUREVIEW | CSUREVIEW | DESIGN FOR NEW TRANSFORMER ALREADY COMPLETED WITH CSU WO#4355615-01. No apparent conflicts.KCL | KLEIBHART@CSU.ORG | Gas/Elec. Utils | 2354825 |
| Construction | Original | N | 9/1/2026 | SHELLEY | SHELLEY | No construction scope | | Construction | 2354755 |
| Enumeration | Original | A | 8/31/2026 | AMY | AMY | A separate address was assigned 3304 E Fountain Blvd. | | Enumeration | 2354409 |
| Electronic Plan | Original | / | 8/31/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2354364 |
| | Original | / | 8/31/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/31/2026 for plan submitted 08/31/2026. Submit Date updated to now. Plan now open for review. | | | 2354332 |
| Energy | Original | N | 8/31/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2354068 |
| Floodplain | Original | N | 8/31/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6422407010) | | Floodplain | 2354067 |