| Energy | Original | D | 10/1/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2365914 |
| Mechanical | Original | D | 10/1/2026 | QUINTONW | QUINTONW | EOR must address all previous disapproval comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2365913 |
| Gas/Elec. Utils | Original | A | 9/28/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts.JL/JF | jluukkonen | Gas/Elec. Utils | 2364474 |
| CO Springs DRE | Original | A | 9/28/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2364444 |
| Electrical | Original | N | 9/28/2026 | CONNERM | CONNERM | | | Electrical | 2364035 |
| Electrical | Original | D | 9/28/2026 | CONNERM | CONNERM | Provide electrical plans. See the following link for requirements:
https://www.pprbd.org/File/ByAlias/ElectricalReview * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2363995 |
| Zoning/Planning | Original | / | 9/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2363973 |
| Electronic Plan | Original | / | 9/28/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2363955 |
| Enumeration | Original | N | 9/28/2026 | BECKYA | BECKYA | | | Enumeration | 2363949 |
| Submittal 2 | Original | / | 9/28/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2363940 |
| Energy | Original | D | 9/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2357620 |
| Plumbing | Original | N | 9/9/2026 | SHANEN | SHANEN | | | Plumbing | 2357619 |
| CO Springs DRE | Original | A | 9/9/2026 | CVANAPPLEDORN | CVANAPPLEDORN | Commercial interior new boilers. Only exterior work are pipes which extend 3' vertically and no more than a foot out. | | CO Springs DRE | 2357387 |
| CSU Water | Original | N | 9/9/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2357357 |
| Electrical | Original | D | 9/8/2026 | CONNERM | CONNERM | Provide electrical plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2357085 |
| Mechanical | Original | D | 9/8/2026 | QUINTONW | QUINTONW | Disapproved: Provide combustion air calculations to coincide with louver size. Provide mechanical comcheck. Schedule new boilers. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2357082 |
| Electronic Plan | Original | / | 9/8/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2357069 |
| Gas/Elec. Utils | Original | D | 9/8/2026 | CSUREVIEW | CSUREVIEW | Submit Electric Load Data Form showing existing and new electric loads to CSU Field Engineering. Form can be found at: https://www.csu.org/hubfs/Document-Library/ElectricLoadData.pdf?hsLang=en JAR | jreuter@csu.org | Gas/Elec. Utils | 2356910 |
| Zoning/Planning | Original | / | 9/4/2026 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2356834 |
| Construction | Original | N | 9/4/2026 | BRIANB | BRIANB | no construction scope indicated | | Construction | 2356685 |
| Electronic Plan | Original | / | 9/4/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2356630 |
| Enumeration | Original | D | 9/4/2026 | BECKYA | BECKYA | This lot contains several buildings with separate addresses, provide a site plan showing all buildings with addresses and highlight area of work.
Update Code Study Form to show missing required information. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2356625 |
| | Original | / | 9/3/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/03/2026 for plan submitted 09/03/2026. Submit Date updated to now. Plan now open for review. | | | 2356476 |
| Energy | Original | / | 9/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2355969 |
| Floodplain | Original | N | 9/3/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6430107009) | | Floodplain | 2355968 |