| Electrical | Original | A | 10/19/2026 | BERTHA | BERTHA | | | Electrical | 2372525 |
| Energy | Original | A | 10/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2372526 |
| Electronic Plan | Original | / | 10/15/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2371627 |
| CSU Electric | Original | A | 10/14/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts.-DT | dytrujillo | CSU Electric | 2370715 |
| Plumbing | Original | A | 10/14/2026 | SHANEN | SHANEN | | | Plumbing | 2370596 |
| | Original | / | 10/13/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2370550 |
| | Original | / | 10/13/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2370530 |
| Submittal 3 | Original | / | 10/13/2026 | TREYW | TREYW | Submittal #3 | | Submittal 3 | 2370527 |
| CO Springs Fire | Original | A | 10/9/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2369153 |
| CO Springs DRE | Original | A | 10/6/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2367407 |
| Energy | Original | D | 10/5/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2366913 |
| Electrical | Original | D | 10/5/2026 | BERTHA | BERTHA | Comply with previous review comment - Comply with Colorado Model Electric Ready and Solar Ready Code. Panel Schedule – provide two or three pole breaker space for each piece of combustion equipment. Floor Plan - provide a receptacle or junction box located near each piece of combustion equipment
Comply with previous review comment - Comply with C405.11 - 2021 IECC - No AMM on file. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2366912 |
| Mechanical | Original | A | 10/2/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2366360 |
| Zoning/Planning | Original | / | 10/2/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2366323 |
| CSU Electric | Original | D | 10/1/2026 | CSUREVIEW | CSUREVIEW | Submit Electric Load Data Form to CSU Field Engineering. Form can be found at: https://www.csu.org/hubfs/Document-Library/ElectricLoadData.pdf?hsLang=en JF | JulianFoster | CSU Electric | 2366175 |
| Plumbing | Original | D | 10/1/2026 | SHANEN | SHANEN | Drinking fountain alternate materials and methods application form fee must be paid prior to processing. Water heater schedule must show efficiency requirements are met per section C404.2. ASHRAE is not a table C404.2 approved test procedure for storage water heaters and is not the performance standard that is required. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2366136 |
| Construction | Original | A | 10/1/2026 | BRIANB | BRIANB | | | Construction | 2366117 |
| Enumeration | Original | A | 10/1/2026 | BECKYA | BECKYA | | | Enumeration | 2365947 |
| Submittal 2 | Original | / | 10/1/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2365934 |
| CO Springs Fire | Original | D | 9/17/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | nickbrown | CO Springs Fire | 2360855 |
| CO Springs Hazmat | Original | N | 9/17/2026 | CSFIRE | CSFIRE | | nickbrown | CO Springs Hazmat | 2360854 |
| CO Springs DRE | Original | A | 9/17/2026 | SSADLER | SSADLER | Commercial interior finish approved. No changes to footprint, parking, landscaping, or use. | | CO Springs DRE | 2360757 |
| CO Springs DRE | Original | D | 9/15/2026 | SSADLER | SSADLER | It appears that the proposed warehouse is a conditional use per the zone district. Schedule a pre application meeting to discuss options. https://aca-prod.accela.com/cosprings/default.aspx | | CO Springs DRE | 2359759 |
| Energy | Original | D | 9/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2359427 |
| Plumbing | Original | D | 9/15/2026 | SHANEN | SHANEN | EWC1 does not comply with section 410.3. Water heater schedule must show efficiency requirements are met per section C404.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2359426 |
| Mechanical | Original | D | 9/15/2026 | TREVORH | TREVORH | Disapproved; Need to add the Refrigeration type to this schedule * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2359422 |
| Electrical | Original | D | 9/15/2026 | BERTHA | BERTHA | Comply with Colorado Model Electric Ready and Solar Ready Code.
Provide conductor size, type and quantity. No EGC.
Comply with C405.11 - 2021 IECC - No AMM on file. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2359278 |
| Elevators | Original | N | 9/14/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2359249 |
| Stormwater | Original | N | 9/14/2026 | GHUNTLEY | GHUNTLEY | Interior finish, does not require SWENT | | Stormwater | 2359125 |
| CSU Contract Admin. | Original | N | 9/14/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees required for this plan set.
AMS | ASweet | CSU Contract Admin. | 2359061 |
| Zoning/Planning | Original | / | 9/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2358759 |
| CSU Water | Original | N | 9/11/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2358600 |
| CSU Waste Water | Original | N | 9/11/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2358597 |
| EPC Health Dept | Original | N | 9/11/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable.GGM | Heagmiranda | EPC Health Dept | 2358560 |
| CSU Gas | Original | A | 9/11/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. | mtelitz | CSU Gas | 2358444 |
| City Engr | Original | N | 9/11/2026 | HVO | HVO | | | City Engr | 2358428 |
| CSU Electric | Original | D | 9/11/2026 | CSUREVIEW | CSUREVIEW | Submit Electric Load Data Form to CSU Field Engineering. Form can be found at: https://www.csu.org/hubfs/Document-Library/ElectricLoadData.pdf?hsLang=en MJG | MikeJG | CSU Electric | 2358421 |
| Energy | Original | / | 9/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2358326 |
| Construction | Original | D | 9/11/2026 | BRIANB | BRIANB | See A0.2 / A1.1 / A2.0 / code study form / IECC certificate * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2358325 |
| Electronic Plan | Original | / | 9/4/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2356709 |
| Enumeration | Original | A | 9/3/2026 | BECKYA | BECKYA | | | Enumeration | 2356413 |
| Electronic Plan | Original | / | 9/3/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2356384 |
| | Original | / | 9/3/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/03/2026 for plan submitted 09/03/2026. Submit Date updated to now. Plan now open for review. | | | 2356317 |
| Energy | Original | / | 9/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2356303 |
| Floodplain | Original | N | 9/3/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307004009) | | Floodplain | 2356302 |