| Fountain Fire | Original | D | 9/30/2026 | CSFIRE | CSFIRE | Wayne from Fountain Fire has concerns about this project due to this being a 2 story, single story building. Also the building has a sprinkler system but Wayne as no record of what the system was designed to. I will get with the RBD reviewer to schedule a meeting for us to discuss this further. Plans have been disapproved pending resolution of these issues. | chiptaylor | Fountain Fire | 2365714 |
| Fountain Fire | Original | A | 9/23/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | Fountain Fire | 2362785 |
| Fountain Hazmat | Original | N | 9/23/2026 | CSFIRE | CSFIRE | | chiptaylor | Fountain Hazmat | 2362783 |
| Energy | Original | D | 9/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2359734 |
| Mechanical | Original | D | 9/15/2026 | TREVORH | TREVORH | Disapproved; 9406 is listed as a Residential town home? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2359733 |
| Electrical | Original | D | 9/15/2026 | DANIELG | DANIELG | Provide conductor size, type, and quantity from utility transformer to the scope of work.
Show service OCPD on the one-line.
Please clarify if there is more than one service on this structure. 230.2 NEC. A-sheets show a separate tenant space. Provide a complete one-line.
Comply with 110.26(D) NEC.
Controlled receptacles must be shown on the plan per C405.11 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2359577 |
| Electronic Plan | Original | / | 9/15/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2359570 |
| Plumbing | Original | D | 9/15/2026 | SHANEN | SHANEN | Enumeration review comments must be addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2359568 |
| Construction | Original | D | 9/15/2026 | BPHILLIPS | BPHILLIPS | Two sets of plans included in architectural file. Remove one, leaving the one intended for construction.See plan for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2359498 |
| Energy | Original | / | 9/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2358507 |
| Electronic Plan | Original | / | 9/10/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2357917 |
| Enumeration | Original | D | 9/9/2026 | BECKYA | BECKYA | The address for the commercial space is 9412 Mosaic Heights. Please update all plan pages to show the correct address.
Also, It appears there are plans in the Architectural Plan set that show 9406 Mountain Heights are these duplicates? The street name is wrong. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2357724 |
| Electronic Plan | Original | / | 9/9/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2357625 |
| | Original | / | 9/9/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/09/2026 for plan submitted 09/03/2026. Submit Date updated to now. Plan now open for review. | | | 2357563 |
| Water Division | Original | / | 9/3/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2356445 |
| Waste Water Div | Original | / | 9/3/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2356446 |
| Energy | Original | / | 9/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2356444 |
| Floodplain | Original | N | 9/3/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5532315003) | | Floodplain | 2356443 |