| Manitou Zoning | Original | D | 10/28/2026 | MSZONING | MSZONING | | eringsred | Manitou Zoning | 2375981 |
| Manitou Water | Original | D | 10/28/2026 | MSWATER | MSWATER | Plans are inconsistent with fixture counts | bschmittcms | Manitou Water | 2375971 |
| Manitou Waste Water | Original | D | 10/28/2026 | MSWATER | MSWATER | Plans are inconsistent with Fixture Counts | bschmittcms | Manitou Waste Water | 2375969 |
| Energy | Original | D | 10/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2375258 |
| Electrical | Original | D | 10/26/2026 | CONNERM | CONNERM | Provide Fault current information (SCCR, AIC, SCA) at all of the following locations in tabular format 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Multi-meter services must include a list of enumerated addresses on the one-line diagram
Provide overcurrent protection for MCB and feeders
Show panel DPEV on one-line
Lighting controls must be clearly shown and must comply with R404.2 and R404.3
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Comply with CO MERSRC: - main electrical service panels for commercial buildings must have a minimum buss bar rating of 200 amps. - Plans must identify at least one "Potential Pathway" for running conduit/raceways from the roof's solar-ready zone to the electrical service panel. -Confirm proposed EVSE are wall- or pedestal-mounted, listed/labeled, and comply with NEC Article 625. They must also have internet connectivity and (if inductive) be ENERGY STAR certified. Must have minimum charging rate of 6.2 kVA (30A at 208/240V)
Provide key for identification of EV spaces (EVSE, EVCL, EVR, EVC)
The EV site plan must indicate at minimum the same number of spots as indicated on the Development Plan.
Complete re-review necessary * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2375257 |
| Electronic Plan | Original | / | 10/26/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2374880 |
| Manitou Hazmat | Original | A | 10/21/2026 | MSFIRE | MSFIRE | Ok per B Dorris | bdorris | Manitou Hazmat | 2373777 |
| Manitou Fire | Original | A | 10/21/2026 | MSFIRE | MSFIRE | Ok per B Dorris | bdorris | Manitou Fire | 2373776 |
| Mechanical | Original | D | 10/7/2026 | TREVORH | TREVORH | Disapproved; Unit tags are not matching the floor plans typical . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2368372 |
| EPC Health Dept | Original | D | 10/6/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2367850 |
| Plumbing | Original | D | 10/6/2026 | SHANEN | SHANEN | Preliminary review. Construction review comments must be addressed. Provide a piping materials schedule on the plumbing plans per PPRBD plan review requirements. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. 3/4" CW is undersized to serve 11.4 wsfu. Make corrections throughout. Provide roof plan to show sizing for roof drains, overflow drains, roof drain conductors, downspouts and overflow scuppers. Provide gpm and/or square footage served by each component of the roof drain system. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2367812 |
| Elevators | Original | N | 10/6/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2367708 |
| Construction | Original | D | 10/5/2026 | MATTHEWA | MATTHEWA | Code study form // Continuity at fire barriers // Architecturals // Life safety plan // Accessible elements // IECC certificates * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2367210 |
| Electronic Plan | Original | / | 9/21/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2361585 |
| Electronic Plan | Original | / | 9/15/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2359648 |
| Enumeration | Original | N | 9/15/2026 | BECKYA | BECKYA | Manitou Planning will assign separate addresses for this development. | | Enumeration | 2359429 |
| Electronic Plan | Original | / | 9/14/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2359069 |
| Electronic Plan | Original | / | 9/14/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2359062 |
| | Original | / | 9/14/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/14/2026 for plan submitted 09/11/2026. Submit Date updated to now. Plan now open for review. | | | 2359009 |
| Energy | Original | / | 9/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2358664 |
| Floodplain | Original | N | 9/11/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7404411024) | | Floodplain | 2358660 |