| SW HWY 115 Fire | Original | A | 11/16/2026 | SWHWY115FIRE | SWHWY115FIRE | This cell site is full of critical infrastructure. The SW Hwy 115 FPD has commented to this applicant in the past that this cell site needs to have major fuels mitigation work done. In its current state, it is not defendable in a fire scenario. | SWhwy115FPD | SW HWY 115 Fire | 2382908 |
| Fire | Original | / | 10/29/2026 | SYSTEM | SYSTEM | Contact Fire department for approval prior to permit | | Fire | 2376802 |
| Electrical | Original | A | 10/29/2026 | CONNERM | CONNERM | | | Electrical | 2376784 |
| Electronic Plan | Original | / | 10/29/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2376674 |
| County Zoning | Original | A | 10/23/2026 | DSDCHAMBERS | DSDCHAMBERS | Approved. Permit approved through EPC Planning NTWR2614. | | County Zoning | 2374551 |
| County Zoning | Original | D | 10/23/2026 | DSDCHAMBERS | DSDCHAMBERS | Prior to the building permit, it is required to acquire a permit from El Paso County Planning and Community Development. Please submit tower modification plans to El Paso County Planning Department for project set up and plan review.
Applicant - initiated through EDARP EDARP ( https://epcdevplanreview.com/)
1. On the website linked above, under "Getting Started", click on "Initiate a minor application." 2. Enter email at the top of the screen. 3. Select "Tower Notice: Mod., Removal, Discontinuance, or Replacement." from the list. 4. Select "Send Code" at the bottom of that page. 5. Check your email for a verification code and complete all next steps.
Planning reviews require both a project statement and site plan. Once county plan review is complete, include approved documents to PPRBD submittal. This is typically a very quick process, often reviewed and approved within 2 days. The application review fee is paid through EDARP and will be $282.00. | | County Zoning | 2374474 |
| Submittal 2 | Original | / | 10/15/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2371397 |
| County Zoning | Original | D | 9/21/2026 | DSDCHAMBERS | DSDCHAMBERS | Please submit tower modification plans to El Paso County Planning Department for project set up and plan review.
Applicant - initiated through EDARP EDARP ( https://epcdevplanreview.com/)
1. On the website linked above, under "Getting Started", click on "Initiate a minor application." 2. Enter email at the top of the screen. 3. Select "Tower Notice: Mod., Removal, Discontinuance, or Replacement." from the list. 4. Select "Send Code" at the bottom of that page. 5. Check your email for a verification code and complete all next steps.
Planning reviews require both a project statement and site plan. Once county plan review is complete, include approved documents to PPRBD submittal. This is typically a very quick process, often reviewed and approved within 2 days. The application review fee is paid through EDARP and will be $282.00. | | County Zoning | 2361821 |
| Zoning/Planning | Original | / | 9/21/2026 | DSDCHAMBERS | DSDCHAMBERS | In Current Review by DSDCHAMBERS | | Zoning/Planning | 2361640 |
| Electrical | Original | D | 9/16/2026 | BERTHA | BERTHA | Provide complete one line to include conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide panel schedules to include volt amps on all branch circuits and calculated load of panel in amps for all panels affected by the scope of work - all panels in the chain of supply.
Provide panel and circuit number on all electrical equipment (new and relocated) . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2360413 |
| Enumeration | Original | N | 9/16/2026 | BECKYA | BECKYA | Drawing power from T-Mobile. | | Enumeration | 2360016 |
| | Original | / | 9/16/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/16/2026 for plan submitted 09/15/2026. Submit Date updated to now. Plan now open for review. | | | 2360000 |
| Construction | Original | N | 9/16/2026 | SHELLEY | SHELLEY | No construction scope | | Construction | 2359907 |
| Electronic Plan | Original | / | 9/16/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2359895 |
| Electronic Plan | Original | / | 9/15/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2359721 |
| Energy | Original | N | 9/15/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2359712 |
| Floodplain | Original | N | 9/15/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7600000276) | | Floodplain | 2359711 |