| Energy | Original | D | 10/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2367414 |
| Mechanical | Original | D | 10/6/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2367413 |
| CO Springs Fire | Original | D | 10/2/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2366533 |
| CO Springs Hazmat | Original | D | 10/2/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2366532 |
| Electrical | Original | D | 9/30/2026 | CONNERM | CONNERM | Provide fault current info (SCA. AIC, SCCR) for all new/refed panels and air conditioning equipment.
Provide series rated information
Controlled receptacles must be shown on the plan per C405.11 OR have approved AM&M
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2365444 |
| Electronic Plan | Original | / | 9/30/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2365421 |
| Plumbing | Original | D | 9/30/2026 | SHANEN | SHANEN | Occupant load required to verify compliance with section 403.1. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All mechanical condensate piping must be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, interceptor/separator locations, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2365376 |
| Elevators | Original | N | 9/30/2026 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2365327 |
| Stormwater | Original | N | 9/28/2026 | GHUNTLEY | GHUNTLEY | Activity does not disturb an acre or more and is not part of a larger common plan of development. | | Stormwater | 2364434 |
| City Engr | Original | D | 9/28/2026 | HVO | HVO | Please see previous comment- include a copy of the approved Development Plan, and street improvement plan (if applicable) | | City Engr | 2364370 |
| CO Springs DRE | Original | D | 9/28/2026 | SSADLER | SSADLER | The development plan is still under review. Once it is approved, upload the final approved and stamped plans, the approval letter, the final recorded plat, and the final landscaping and irrigation plans. Impact fees are due prior to building permit issuance. | | CO Springs DRE | 2364277 |
| Zoning/Planning | Original | / | 9/25/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2363848 |
| CSU Gas | Original | A | 9/25/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts.JL | jluukkonen | CSU Gas | 2363845 |
| CSU Contract Admin. | Original | D | 9/25/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. Contact our office at 719-668-8111 for an estimate. JMD
CWMSF can be found at https://www.csu.org/Pages/development-files-forms.aspx | jdemello | CSU Contract Admin. | 2363840 |
| CSU Electric | Original | A | 9/25/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RD | RDuran | CSU Electric | 2363803 |
| CSU Water | Original | D | 9/25/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. mjg | mgackle | CSU Water | 2363799 |
| CSU Waste Water | Original | D | 9/25/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2363798 |
| Construction | Original | D | 9/25/2026 | DOUGC | DOUGC | CSF // Architectural // IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2363750 |
| Energy | Original | / | 9/25/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2363749 |
| Electronic Plan | Original | / | 9/25/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2363659 |
| Enumeration | Original | D | 9/18/2026 | BRENT | BRENT | No wrecking permit has been issued for the existing building on this parcel. Enumerations approval pending issuance of a wrecking permit * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2361288 |
| Electronic Plan | Original | / | 9/18/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2361269 |
| | Original | / | 9/18/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/18/2026 for plan submitted 09/18/2026. Submit Date updated to now. Plan now open for review. | | | 2361179 |
| Energy | Original | N | 9/18/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2361172 |
| Floodplain | Original | N | 9/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6327119010) | | Floodplain | 2361170 |