| Energy | Original | D | 10/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2367585 |
| Mechanical | Original | D | 10/6/2026 | TREVORH | TREVORH | Disapproved; Need to indicate on plans how new roof top equipment will be accessed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2367584 |
| Electronic Plan | Original | / | 10/6/2026 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2367555 |
| CO Springs Fire | Original | D | 10/6/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2367492 |
| CO Springs Hazmat | Original | D | 10/6/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2367491 |
| CO Springs DRE | Original | D | 10/2/2026 | SSADLER | SSADLER | Upload the code study form. | | CO Springs DRE | 2366375 |
| EPC Health Dept | Original | D | 9/30/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2365390 |
| CSU Waste Water | Original | D | 9/29/2026 | CSUREVIEW | CSUREVIEW | Contact CSU Industrial Pretreatment representative Bob Bowren via email at fog@csu.org to determine if a variance for an interior grease interceptor is applicable. If applicable, provide a copy of the Variance letter in the building plan set.MDA | malcuran | CSU Waste Water | 2364990 |
| CSU Water | Original | N | 9/29/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow preventer compliant.MDA | malcuran | CSU Water | 2364988 |
| Plumbing | Original | D | 9/29/2026 | SHANEN | SHANEN | This sheet reviewed only for the items that pertain to the plumbing scope. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Provide required CSU variance letter for the indoor grease trap. Contact Robert Bowren at 719-668-1735 or fog@csu.org. CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. Slope of grease waste piping shall be per section 704.1. Schedule prep room and concession plumbing fixtures. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Provide water heater minimum performance (energy factor/thermal efficiency) see table C404.2. Provide a water heater detail to show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. Provide detail for water heater platform construction or schedule manufactured platform. Provide details to show prep room and concession plumbing fixtures are section 802 compliant. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2364976 |
| Zoning/Planning | Original | / | 9/29/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2364973 |
| Electrical | Original | D | 9/29/2026 | CONNERM | CONNERM | Provide fault current info (SCCR, SCA) for new/refed air conditioning equipment
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
All new and existing electrical devices must comply with ANSI 117.1 section 308 reach range. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2364969 |
| Electronic Plan | Original | / | 9/29/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2364936 |
| Construction | Original | D | 9/29/2026 | DOUGC | DOUGC | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2364914 |
| Electronic Plan | Original | / | 9/28/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2364175 |
| Enumeration | Original | D | 9/22/2026 | BRENT | BRENT | The document submitted under the page type of Code Study Form, is not the code study form. Submit the correct, completed form. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2362032 |
| Electronic Plan | Original | / | 9/22/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2362018 |
| | Original | / | 9/22/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/22/2026 for plan submitted 09/22/2026. Submit Date updated to now. Plan now open for review. | | | 2362008 |
| Energy | Original | / | 9/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2361993 |
| Floodplain | Original | N | 9/22/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308016025) | | Floodplain | 2361991 |