| Electrical | Original | D | 11/20/2026 | CONNERM | CONNERM | Indicate service conductor type-CU or AL * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2384957 |
| Electronic Plan | Original | / | 11/20/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2384923 |
| CSU Waste Water | Original | D | 11/19/2026 | CSUREVIEW | CSUREVIEW | Plumbing plans and Utility Construction Drawings do not match for the sanitary service line scope. The entry points to the building do not match and the pipe sizes do not match. Please update as needed. SSH | SHillman | CSU Waste Water | 2384571 |
| CSU Water | Original | A | 11/19/2026 | CSUREVIEW | CSUREVIEW | Comments addressed. SSH | SHillman | CSU Water | 2384570 |
| Mechanical | Original | D | 11/19/2026 | DALEH | DALEH | Still need cooler/freezer refrigeration calculations prior to mechanical approval * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2384479 |
| CSU Contract Admin. | Original | D | 11/19/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 2384264 |
| Zoning/Planning | Original | / | 11/19/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2384225 |
| City Engr | Original | A | 11/19/2026 | DSOSA | DSOSA | Previous Engineering comments addressed. No further comments from EDR. | | City Engr | 2384186 |
| Construction | Original | D | 11/19/2026 | SHELLEY | SHELLEY | Foundation design must reference soils report and correct bearing. Not required to be stamped to State DOH. DO NOT REPLACE DOCUMENTS THAT REQUIRE NO CORRECTIONS.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2384148 |
| Enumeration | Original | A | 11/18/2026 | AMY | AMY | | | Enumeration | 2384050 |
| Electronic Plan | Original | / | 11/18/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2384040 |
| Submittal 3 | Original | / | 11/18/2026 | TREYW | TREYW | Submittal #3 | | Submittal 3 | 2383893 |
| EPC Health Dept | Original | A | 11/6/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable to Air Quality program. Per Tim Mathis, Project Leader, project is only earthmoving 0.94 acres of land.
Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AB | abrannon | EPC Health Dept | 2379491 |
| CO Springs Fire | Original | A | 11/3/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2377824 |
| CO Springs Hazmat | Original | N | 11/3/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2377823 |
| CO Springs DRE | Original | D | 11/2/2026 | SSADLER | SSADLER | Upload the final approved development plan. Upload the final approved landscaping and irrigation plans. Upload the final recorded plat. All impact fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2377284 |
| Energy | Original | D | 10/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2376924 |
| Mechanical | Original | D | 10/30/2026 | DALEH | DALEH | It appears the crawl space is intended to be a conditioned crawl space per 2021 IMC 406 It appears the design does not meet this section. Exhaust fans are required to terminate to the exterior. Crawl would need to be provided with a supply register Provide refrigeration calculations for walk in cooler unless cooler is equipped with sensors and alarms * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2376923 |
| EPC Health Dept | Original | D | 10/30/2026 | HEALTHDEPT | HEALTHDEPT | Per AB, retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted.
Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2376906 |
| Plumbing | Original | A | 10/29/2026 | SHANEN | SHANEN | State of CO DOH approved plans. | | Plumbing | 2376640 |
| City Engr | Original | D | 10/29/2026 | DSOSA | DSOSA | Please upload the approved Development Plan | | City Engr | 2376535 |
| Electronic Plan | Original | / | 10/29/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2376533 |
| Stormwater | Original | A | 10/29/2026 | GHUNTLEY | GHUNTLEY | | | Stormwater | 2376472 |
| CSU Water | Original | D | 10/29/2026 | CSUREVIEW | CSUREVIEW | Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Water | 2376425 |
| CSU Waste Water | Original | D | 10/29/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2376424 |
| CSU Gas | Original | A | 10/29/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts.jl | jluukkonen | CSU Gas | 2376401 |
| Electrical | Original | D | 10/29/2026 | BERTHA | BERTHA | Indicate conductor type - CU or AL
Provide withstand rating for all equipment in the fault current calculations table.
Provide fault current information for air conditioning / refrigeration equipment. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2376384 |
| CSU Electric | Original | A | 10/28/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. MJG | MikeJG | CSU Electric | 2376336 |
| Zoning/Planning | Original | / | 10/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2376333 |
| CSU Contract Admin. | Original | D | 10/28/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. JMD | jdemello | CSU Contract Admin. | 2376282 |
| Construction | Original | D | 10/28/2026 | SHELLEY | SHELLEY | Soils report required. Provide and reference. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2376270 |
| Enumeration | Original | A | 10/28/2026 | AMY | AMY | 1 Plan 2 Permits required. Cooler address is 1344 Interquest Pkwy. | | Enumeration | 2375924 |
| Electronic Plan | Original | / | 10/28/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2375923 |
| Submittal 2 | Original | / | 10/27/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2375448 |
| Plan Coordinator (Main) | Original | D | 10/6/2026 | SHELLEY | SHELLEY | Disapprove all remaining departments to allow plan to be resubmitted - SEE CONSTRUCTION COMMENTS. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2367479 |
| Construction | Original | D | 10/6/2026 | SHELLEY | SHELLEY | Plan is incomplete and incorrectly submitted. Review stopped. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2367478 |
| Electronic Plan | Original | / | 10/6/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2367469 |
| Enumeration | Original | A | 10/5/2026 | AMY | AMY | | | Enumeration | 2367075 |
| | Original | / | 10/5/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/05/2026 for plan submitted 10/01/2026. Submit Date updated to now. Plan now open for review. | | | 2366777 |
| Electronic Plan | Original | / | 10/2/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2366502 |
| Energy | Original | / | 10/1/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2366210 |
| Floodplain | Original | N | 10/1/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220112005) | | Floodplain | 2366209 |