PROCESSING....
This is hidden content to make Wave think this is not a heading
Skip to main content
Pikes Peak Regional Building Department
Ensuring life safety and welfare of our community through efficient and consistent application of adopted codes and standards.
Home
Contact
Search
Accessibility
Cart
Sign In
Home
Contact
Search
Accessibility
Cart
Sign In
Plan Details
Clear
Permits
By Address
By Permit Number
Fee Calculator
Plans
By Address
List of Plans
Home
Plan #
  
Type
 
Plan
Owner
Address
719 E KIOWA ST, COLORADO SPRINGS, CO 80903
Parcel Info
6417216012
Truss P/SF
30 (Elevation: 5,994 Feet)
Project
SERVICE UPGRADE (
437
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
COLORADO SPRINGS FIRE DIST
Submit Date
Approval Date
Location
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 4
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Electrical
D
0
E
Electrical
Energy
N
G
Energy
Enumeration
D
0
N
Enumeration
Floodplain
N
W
Floodplain
Log Entries: 7
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
Electrical
Original
D
10/8/2026
CONNERM
CONNERM
Provide fault current info (SCA, AIC) for all new panels
Provide panel schedules with volt amps on all branch circuits and calculated load of panel in amps
Show compliance with 250.66
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Electrical
2368724
Electronic Plan
Original
/
10/8/2026
CONNERM
CONNERM
In Current Review by CONNERM
Electronic Plan
2368711
Enumeration
Original
D
10/8/2026
BECKYA
BECKYA
The plan was submitted under 719 E Kiowa St, Code Study Form says 729 E Kiowa St, Site plan says 727 E Kiowa St. Clarify address for this scope and add Legal Description to the Code Study Form. Duplex is not a Legal Description.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Enumeration
2368707
Electronic Plan
Original
/
10/8/2026
BECKYA
BECKYA
In Current Review by BECKYA
Electronic Plan
2368699
Original
/
10/8/2026
SYSTEM
SYSTEM
Plan Review fees paid 10/08/2026 for plan submitted 10/07/2026. Submit Date updated to now. Plan now open for review.
2368661
Energy
Original
N
10/7/2026
SYSTEM
SYSTEM
Energy Department review not required under 2023 PPRBC when IECC is N/A
Energy
2368241
Floodplain
Original
N
10/7/2026
RBD GIS
RBD GIS
Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6417216012)
Floodplain
2368240