| Zoning/Planning | Original | / | 10/12/2026 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2369661 |
| Plumbing | Original | D | 10/12/2026 | SHANEN | SHANEN | Sanitary sewer sizing does not match referenced civil drawings. Water service sizing does not match referenced civil drawings. Provide water heater minimum performance (energy factor/thermal efficiency) see table C404.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2369589 |
| Electrical | Original | D | 10/12/2026 | BERTHA | BERTHA | Provide fault current information (SCCR, AIC, SCA) - in tabular format - at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide series rated listed combinations.
Provide column seal off detail - Comply with 514.9 NEC
Provide dimension indicating compliance with 514.11 NEC
Provide location of all electrical equipment with panel and circuit number on plan view.
Provide electrical plans with room names.
Comply with 2021 IECC
Recessed lighting must be shown on the lighting schedule and indicate compliance with C402.5.10.
Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3.
For mechanical systems located outside of a building, verify controls comply with C403.13.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Comply with Colorado Model Electric Ready Solar Ready Code
Panel Schedules – two or three pole breaker space for each piece of combustion equipment indicating an equivalent electrical heating load or future heat pump.
Floor Plan - receptacle or junction box located near each piece of combustion equipment with no physical obstructions.
Labeling - Confirm the junction box, receptacle, and dedicated panel breaker spaces are clearly labeled for their intended future use.
Panel Schedule – two pole breaker space at the bottom of the buss labeled “For Future Solar Electric.”
Floor plan - Plans must identify at least one "Potential Pathway" for running conduit/raceways from the roof's solar-ready zone to the electrical service panel.
EV Site Plan: The EV site plan must clearly indicate the location and type of EV spot. The EV site plan must indicate at minimum the same number of spots as indicated on the Development Plan.
Complete re-review necessary. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2369548 |
| Electronic Plan | Original | / | 10/12/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2369543 |
| Electronic Plan | Original | / | 10/12/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2369539 |
| Elevators | Original | N | 10/9/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2369457 |
| CSU Contract Admin. | Original | N | 10/9/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due, only in CSU gas territory. BS | bschifferstein | CSU Contract Admin. | 2369399 |
| CSU Gas | Original | A | 10/9/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. | mtelitz | CSU Gas | 2369378 |
| CSU Electric | Original | D | 10/9/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. Please contact PPRBD for Service provider in this area. KCL | KLEIBHART@CSU.ORG | CSU Electric | 2369316 |
| EPC Health Dept | Original | D | 10/9/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly.
Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH.
For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2369298 |
| Construction | Original | D | 10/9/2026 | BRIANB | BRIANB | see code study form / sheets A1.5 / A2.3 / A2.8 / IECC certificate * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2369268 |
| Electronic Plan | Original | / | 10/9/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2369005 |
| Enumeration | Original | D | 10/8/2026 | BRENT | BRENT | The final plat for Waterview East Commercial Fil. No. 1 has not been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2368801 |
| | Original | / | 10/8/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/08/2026 for plan submitted 10/07/2026. Submit Date updated to now. Plan now open for review. | | | 2368643 |
| Electronic Plan | Original | / | 10/7/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2368379 |
| Fire | Original | / | 10/7/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2368377 |
| Hazmat | Original | / | 10/7/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2368376 |
| Energy | Original | / | 10/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2368375 |
| Floodplain | Original | N | 10/7/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5509200004) | | Floodplain | 2368374 |