Electrical | Original | D | 4/14/2022 | RICHG | RICHG | Comply with 706.15
Comply with 706.31 (F) (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1665475 |
Electronic Plan | Original | / | 4/14/2022 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1665452 |
Construction | Original | A | 4/14/2022 | DANM | DANM | | | Construction | 1665041 |
Electronic Plan | Original | / | 4/14/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1665039 |
Resubmittal 6 | Original | / | 4/13/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #6 | | Resubmittal 6 | 1664754 |
Electrical | Original | D | 3/31/2022 | RICHG | RICHG | Comply with previous comments. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1658662 |
Resubmittal 5 | Original | / | 3/30/2022 | BPHILLIPS | BPHILLIPS | Resubmittal #5 | | Resubmittal 5 | 1657882 |
Electrical | Original | D | 3/16/2022 | RICHG | RICHG | Comply with 706.31(F)
Ess is the output of the inverter- see 706.2 definitions
Address previous review comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1651192 |
Electronic Plan | Original | / | 3/16/2022 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1651131 |
Construction | Original | A | 3/14/2022 | DANM | DANM | | | Construction | 1649600 |
Electronic Plan | Original | / | 3/14/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1649599 |
Resubmittal 4 | Original | / | 3/14/2022 | AUSTINK | AUSTINK | Resubmittal #4 | | Resubmittal 4 | 1649127 |
Electrical | Original | D | 2/22/2022 | SHELBY | SHELBY | Label individual components on floor plan. Comply 706.31(F) NEC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1639938 |
Electronic Plan | Original | / | 2/22/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1639919 |
Construction | Original | D | 2/11/2022 | DANM | DANM | The submitted site plan is for the incorrect address.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1636077 |
Electronic Plan | Original | / | 2/11/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1636057 |
Resubmittal 3 | Original | / | 2/11/2022 | AUSTINK | AUSTINK | Resubmittal #3 | | Resubmittal 3 | 1635921 |
Electrical | Original | D | 12/1/2021 | SHELBY | SHELBY | Previous review comments have not been addressed. See circled areas on site plan and one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1601390 |
Construction | Original | A | 12/1/2021 | DANM | DANM | | | Construction | 1601042 |
Electronic Plan | Original | / | 12/1/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1601041 |
Resubmittal 2 | Original | / | 12/1/2021 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1601020 |
Electrical | Original | D | 11/29/2021 | SHELBY | SHELBY | 1.Floor plan must include all components in this scope of work. 2. Items on the floor plan must be labeled the same on the floor plan and the one line. Complete re review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1599857 |
Electronic Plan | Original | / | 11/29/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1599856 |
Construction | Original | A | 11/19/2021 | DANM | DANM | | | Construction | 1597073 |
Electronic Plan | Original | / | 11/19/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1597068 |
Resubmittal 1 | Original | / | 11/19/2021 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1596928 |
Electrical | Original | D | 10/20/2021 | SHELBY | SHELBY | 1. Installation of Energy Storage Systems (ESS) requires both a floor plan and site plan submittal. On the floor plan please clearly indicate exterior walls and interior walls and the location of all electrical gear. All electrical gear must be uniquely identified and labeled ( Disconnects). Labeling of electrical gear must match throughout the plan set. Please submit the required floor plan under the “Other” category. 2. Installation must comply with 706.15(A)(3) NEC and 706.31(F) NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1581506 |
Electronic Plan | Original | / | 10/20/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1581505 |
CO Springs DRE | Original | N | 10/14/2021 | PDOSCH | PDOSCH | Flush mount solar panels and/or PV solar panels do not exceed the maximum residential height requirements | | CO Springs DRE | 1579015 |
Zoning/Planning | Original | / | 10/14/2021 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1579014 |
Construction | Original | A | 10/14/2021 | DANM | DANM | | | Construction | 1578947 |
Electronic Plan | Original | / | 10/14/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1578942 |
Floodplain | Original | N | 10/14/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6336113001) | | Floodplain | 1578761 |