Electrical | Original | D | 6/17/2022 | RICHG | RICHG | 1. Service conductors are under size for 200 amp breaker in the main service panel.
2. No ground in service conductors.
3. Provide updated CSU utility letter. The one on file has been expired since 2/2022 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1700211 |
Construction | Original | A | 6/16/2022 | LBENNETT | LBENNETT | | | Construction | 1699539 |
Electronic Plan | Original | / | 6/16/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1699538 |
Resubmittal 5 | Original | / | 6/15/2022 | ANDREAL | ANDREAL | Resubmittal #5 | | Resubmittal 5 | 1698597 |
Electrical | Original | D | 1/14/2022 | SHELBY | SHELBY | Previous review comments have not been addressed. Please schedule a walk through review for consultation. PPRBD.ORG. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1621948 |
Construction | Original | A | 1/11/2022 | DANM | DANM | | | Construction | 1620065 |
Electronic Plan | Original | / | 1/11/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1620062 |
Resubmittal 4 | Original | / | 1/11/2022 | AUSTINK | AUSTINK | Resubmittal #4 | | Resubmittal 4 | 1619930 |
Electrical | Original | D | 1/3/2022 | SHELBY | SHELBY | Previous review comments have not been addressed. The intent of the floor plan is to show where each component is located individually and compare that to the component location on the one line. Labeling must be specific for each component and must be the same on floor plan and one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1616022 |
Electronic Plan | Original | / | 1/3/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1616021 |
Construction | Original | A | 12/29/2021 | DANM | DANM | | | Construction | 1614462 |
Electronic Plan | Original | / | 12/29/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1614459 |
Resubmittal 3 | Original | / | 12/29/2021 | AUSTINK | AUSTINK | Resubmittal #3 | | Resubmittal 3 | 1613947 |
Electrical | Original | D | 12/3/2021 | SHELBY | SHELBY | 1. Floor plan must show all new electrical equipment in this scope of work. 2. Electrical equipment must be labeled the same on floor plan and one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1602688 |
Electronic Plan | Original | / | 12/3/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1602684 |
Construction | Original | A | 12/2/2021 | DANM | DANM | | | Construction | 1601555 |
Electronic Plan | Original | / | 12/2/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1601551 |
Resubmittal 2 | Original | / | 12/1/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1601444 |
Electrical | Original | D | 11/12/2021 | SHELBY | SHELBY | 1. Missing floor plan. Label electrical equipment on floor and site plan to match labeling on one line. Do not use redundant labeling;for example if you have more than one A/C disconnect label them Disconnect A and Disconnect B etc. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1593078 |
Electronic Plan | Original | / | 11/12/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1593046 |
Construction | Original | A | 11/9/2021 | DANM | DANM | | | Construction | 1591074 |
Electronic Plan | Original | / | 11/9/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1591071 |
Resubmittal 1 | Original | / | 11/9/2021 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1591030 |
Electrical | Original | D | 10/20/2021 | SHELBY | SHELBY | 1. Installation of Energy Storage Systems (ESS) requires both a floor plan and site plan submittal. On the floor plan please clearly indicate exterior walls and interior walls and the location of all electrical gear. All electrical gear must be uniquely identified and labeled ( Disconnects). Labeling of electrical gear must match throughout the plan set. Please submit the required floor plan under the “Other” category. 2. Installation must comply with 706.15(A)(3) NEC and 706.31(F) NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1581512 |
Electronic Plan | Original | / | 10/20/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1581510 |
CO Springs DRE | Original | N | 10/14/2021 | PDOSCH | PDOSCH | Flush mount solar panels and/or PV solar panels do not exceed the maximum residential height requirements | | CO Springs DRE | 1579008 |
Zoning/Planning | Original | / | 10/14/2021 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1579006 |
Construction | Original | A | 10/14/2021 | DANM | DANM | | | Construction | 1578962 |
Electronic Plan | Original | / | 10/14/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1578957 |
Floodplain | Original | N | 10/14/2021 | KEITH | KEITH | | | Floodplain | 1578770 |
Floodplain | Original | / | 10/14/2021 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6326104010) | | Floodplain | 1578765 |