Electrical | Original | D | 11/19/2021 | DANIELG | DANIELG | 1. Installation must comply with 230.85 NEC.
2. Remove parallel neutral (ground) from PV service conductors.
3. Provide service rated PV disconnect with N-G bond.
4. Comply 705.11(B) NEC. Neutral conductor is undersized.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1596892 |