Electrical | Original | D | 4/14/2022 | DANIELG | DANIELG | Please see one-line for comment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1665032 |
Electronic Plan | Original | / | 4/14/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1665012 |
Construction | Original | A | 4/13/2022 | CGIECK | CGIECK | | | Construction | 1664882 |
Electronic Plan | Original | / | 4/13/2022 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1664868 |
Resubmittal 3 | Original | / | 4/13/2022 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1664777 |
Electrical | Original | D | 4/5/2022 | DANIELG | DANIELG | Comply 706.31(F) NEC. Please see one-line for comment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1660354 |
Electronic Plan | Original | / | 4/5/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1660344 |
Construction | Original | A | 4/4/2022 | CGIECK | CGIECK | | | Construction | 1660000 |
Resubmittal 2 | Original | / | 4/4/2022 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 1659813 |
Electrical | Original | D | 2/15/2022 | DANIELG | DANIELG | 1. Engineer stamp is covering labels for electrical gear.
2. Nomenclature must match throughout the plan set. Where is the back-up loads panel?
3. Comply 706.31(F) NEC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1637350 |
Electronic Plan | Original | / | 2/15/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1637338 |
Construction | Original | A | 2/15/2022 | CGIECK | CGIECK | | | Construction | 1637012 |
Electronic Plan | Original | / | 2/15/2022 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1636978 |
Resubmittal 1 | Original | / | 2/14/2022 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1636613 |
Electrical | Original | D | 1/3/2022 | DANIELG | DANIELG | 1. On the floor plan all electrical gear must be uniquely identified and labeled ( Disconnects). Labeling of electrical gear must match throughout the plan set. Please submit the required floor plan under the “Other” category.
2. Installation must comply with 706.31(F) NEC.
3. Provide spec-sheet for back-up gateway.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1615860 |
Electronic Plan | Original | / | 1/3/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1615836 |
CO Springs DRE | Original | N | 12/30/2021 | CHUDSPETH | CHUDSPETH | Flush mount roof solar panels and/or PV solar panels do not exceed maximum residential height requirements | | CO Springs DRE | 1615129 |
Zoning/Planning | Original | / | 12/30/2021 | CHUDSPETH | CHUDSPETH | In Current Review by CCORCORAN | | Zoning/Planning | 1615082 |
Construction | Original | D | 12/30/2021 | CGIECK | CGIECK | (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1614895 |
Electronic Plan | Original | / | 12/30/2021 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1614893 |
Floodplain | Original | N | 12/29/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318213023) | | Floodplain | 1614494 |