Electrical | Original | A | 2/23/2022 | DANIELG | DANIELG | | | Electrical | 1640457 |
Electronic Plan | Original | / | 2/23/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1640446 |
Construction | Original | A | 2/22/2022 | LBENNETT | LBENNETT | | | Construction | 1639944 |
Electronic Plan | Original | / | 2/22/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1639936 |
Submittal 2 | Original | / | 2/17/2022 | AUSTINK | AUSTINK | Submittal #2 | | Submittal 2 | 1638219 |
Electrical | Original | D | 1/13/2022 | DANIELG | DANIELG | 1. Site-plan must match one-line diagram.
2. Provide document showing the rack and modules have been evaluated (by an NRTL) together as a system for grounding the modules per 690.43 NEC (Usually found in the rack installation manual).
3. Remove ground from PV service conductors.
4. Provide service rated PV disconnect with N-G bond.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1621263 |
Electronic Plan | Original | / | 1/13/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1621258 |
CO Springs DRE | Original | N | 1/6/2022 | ESHAFER | ESHAFER | Flush mount solar panels and/or PV solar panels do not exceed the maximum residential height requirements. (see full review) | | CO Springs DRE | 1617883 |
Zoning/Planning | Original | / | 1/6/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1617882 |
Construction | Original | D | 1/6/2022 | SHELLEY | SHELLEY | Provide Unirac configuration report for installation. This is not the correct documentation for the attachment to the roof. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1617857 |
Floodplain | Original | N | 1/6/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6427411018) | | Floodplain | 1617640 |