CO Springs Fire | Original | D | 10/17/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | rpeterson | CO Springs Fire | 2074046 |
CO Springs DRE | Original | D | 10/4/2024 | MAMBUUL | MAMBUUL | Previous comments not addressed. 1. Need to provide financial assurances for public and private improvements. 2. Need to pay CDI, park, school, fire, and police fees. Contact DREplanninginfo@coloradosprings.gov to pay fees. | | CO Springs DRE | 2068675 |
Energy | Original | D | 10/4/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2068399 |
Electrical | Original | A | 10/4/2024 | RICHG | RICHG | | | Electrical | 2068398 |
Mechanical | Original | D | 10/4/2024 | TCRIPPEN | TCRIPPEN | Disapproved:Provide better refrigerant drawings clarify if lines are in the walls or on the outside of the walls and covered you can only penetrate one floor or ceiling than after that a shaft would be required with ventilation. See new code requirements, Chapter 11 of the IMC 2021 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2068364 |
CSU Water | Original | D | 10/4/2024 | CSUREVIEW | CSUREVIEW | 1. CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
2. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. NOTE: Utility Service Plan currently proposed 1" HDPE service line. Verify with plumber that 1" HDPE is sufficient for internal plumbing.
3. It appears that the water service layout and locations do not match utility service plan. Coordinate with civil engineer to ensure they match between USP and plumbing plans. SSM | stefanm | CSU Water | 2068298 |
CSU Waste Water | Original | D | 10/4/2024 | CSUREVIEW | CSUREVIEW | 1. CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
2. Wastewater service layout and locations don't match utility service plans. Coordinate with Civil Engineer to ensure they match. SSM | stefanm | CSU Waste Water | 2068294 |
City Engr | Original | D | 10/4/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2068183 |
Plumbing | Original | A | 10/4/2024 | SHANEN | SHANEN | | | Plumbing | 2068151 |
Stormwater | Original | A | 10/3/2024 | JLANDON | JLANDON | | | Stormwater | 2068108 |
Zoning/Planning | Original | / | 10/3/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2068078 |
CSU Contract Admin. | Original | D | 10/3/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as before - Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. JMD | jdemello | CSU Contract Admin. | 2068064 |
Construction | Original | D | 10/3/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2067942 |
Enumeration | Original | A | 10/3/2024 | BECKYA | BECKYA | | | Enumeration | 2067829 |
Submittal 2 | Original | / | 10/2/2024 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2067233 |
CO Springs Fire | Original | D | 8/27/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2052163 |
Energy | Original | D | 8/14/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2046773 |
Electrical | Original | D | 8/14/2024 | RICHG | RICHG | Panel cannot be in rated assembly.
Comply with R404.3 IECC 2021
Comply with R404.2 IECC 2021
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2046772 |
CO Springs DRE | Original | D | 8/14/2024 | SSADLER | SSADLER | Public and private assurances need to be posted prior to building permit release. PLDO fees are due and need to be paid prior to building permit release. | | CO Springs DRE | 2046532 |
Stormwater | Original | D | 8/14/2024 | JLANDON | JLANDON | Please upload approved final phase Grading and Erosion Control Plan showing retaining wall locations and top of wall/bottom of wall elevations. Locations and elevations should match between Development Plan and GEC Plan | | Stormwater | 2046492 |
City Engr | Original | D | 8/13/2024 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2045914 |
Mechanical | Original | D | 8/13/2024 | TCRIPPEN | TCRIPPEN | Disapproved:GREATER THAN OR EQUAL TO 95 AFUE FURNACE AND 16 SEER AIR CONDITIONER. PER THE IECC R408.2.2 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2045790 |
CSU Contract Admin. | Original | D | 8/12/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/extrx/util_dev_svcs/svc_standards/water/chapter/wp_8.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. BS | bschifferstein | CSU Contract Admin. | 2045624 |
Electronic Plan | Original | / | 8/12/2024 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 2045596 |
Health Dept. | Original | N | 8/12/2024 | HEALTHDEPT | HEALTHDEPT | Colorado Department of Health and Environment Air Pollutant Emission Notice (APEN) may be required for projects earthmoving > 25 acres. Contact CDPHE for more information or visit their website at https://cdphe.colorado.gov/apens-and-air-permits/do-you-need-an-apen-or-air-permit. KB | KBauer | Health Dept. | 2045527 |
CSU Water | Original | D | 8/12/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------ Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. MLW | mlwilliams | CSU Water | 2045493 |
CSU Waste Water | Original | D | 8/12/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. MLW | mlwilliams | CSU Waste Water | 2045490 |
Gas/Elec. Utils | Original | A | 8/12/2024 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. MLW | mlwilliams | Gas/Elec. Utils | 2045488 |
Zoning/Planning | Original | / | 8/12/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2045466 |
Plumbing | Original | D | 8/12/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2045446 |
Construction | Original | D | 8/12/2024 | CGIECK | CGIECK | Please review progress set. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2045435 |
Electronic Plan | Original | / | 7/22/2024 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 2035380 |
Enumeration | Original | D | 7/22/2024 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2035279 |
Electronic Plan | Original | / | 7/19/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2034967 |
Floodplain | Original | N | 7/19/2024 | KEITH | KEITH | this NA/Approveal is for the building only and site work outside the floodplain, channel improvements will require an approved CLOMR and separate floodplain permit through RBD-Floodplain office | | Floodplain | 2034727 |
Energy | Original | / | 7/16/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2033247 |
Floodplain | Original | / | 7/16/2024 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7336200021) | | Floodplain | 2033246 |
Fire | Original | / | 7/16/2024 | RBD GIS | RBD GIS | Parcel 7336200021 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 2033244 |
Stormwater | Original | / | 7/16/2024 | SYSTEM | SYSTEM | Parcel 7336200021 is within the Hillside Overlay (HS). Stormwater Review is required. | | Stormwater | 2033245 |