Out to Review | Original | / | 10/17/2024 | NELIDA | NELIDA | Don 719-888-0362 | | Out to Review | 2074315 |
Finished Bin (Main) | Original | / | 10/16/2024 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2073699 |
City Engr | Original | D | 10/16/2024 | JDAGNILLO | JDAGNILLO | There is an existing geological hazard report on file for this subdivision, written March 9, 1999 by CTL Thompson. Please submit a validation letter from a geotechnical engineer, which confirms the findings of the original report and recommends additional mitigation measures, if applicable, for this project. Submit this letter into our Project Dox system. Below is a link to ProjectDox and a user manual.
https://coloradosprings.gov/stormwater/planreview
Once approved by Engineering Development Review, insert a copy of the approved letter into the building permit plan set for City Engineering sign-off. Thank you
plans routed to RBD | | City Engr | 2073691 |
Stormwater | Original | D | 10/14/2024 | JLANDON | JLANDON | Please add a disclaimer statement that no grading or vegetation removal is allowed If any grading or vegetation removal is taking place, please submit a Hillside plan that includes the following: -Show and label Limits of Disturbance. -Show and label existing and proposed contours (min. 2') and label with elevations. -Show and label soil stockpile within limits of disturbance. -Show stormwater flow arrows. -Include contours, flow arrows, etc. in legend. -PE sign and stamp. | | Stormwater | 2072054 |
City Engr | Original | / | 10/10/2024 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 2071048 |
Plan Coordinator | Original | / | 10/10/2024 | | KSCHOTT | Location = Plan Coordinator by KSCHOTT | | Plan Coordinator | 2071021 |
CO Springs DRE | Original | D | 10/10/2024 | KSCHOTT | KSCHOTT | 1. Even though proposing a 2nd story addition, still need an overall site plan with property boundaries and existing footprint and limit of disturbance boundary. 2. Include hillside disclaimer on site plan and include notes "no grading, vegetation removal, no change to existing footprint and no change to existing drainage patterns." 3. On elevation drawings: include overall max allowable height envelope of 35' measured from the existing grade kerri.schott@coloradosprings.gov (see full review) | | CO Springs DRE | 2071020 |
Zoning/Planning | Original | / | 10/8/2024 | | KSCHOTT | Location = Zoning/Planning by KSCHOTT | | Zoning/Planning | 2069983 |
CO Springs Fire | Original | D | 10/8/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2069858 |
Fire | Original | / | 9/27/2024 | | MAMBUUL | Location = Fire by MAMBUUL | | Fire | 2065603 |
Zoning/Planning | Original | / | 9/26/2024 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2064828 |
Energy | Original | D | 9/26/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2064810 |
Plumbing | Original | D | 9/26/2024 | TCRIPPEN | TCRIPPEN | See plumbing example in plan set, 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2064809 |
Plan Coordinator (Main) | Original | / | 9/26/2024 | | TCRIPPEN | Location = Plan Coordinator (Main) by TCRIPPEN | | Plan Coordinator (Main) | 2064803 |
Mechanical | Original | D | 9/26/2024 | TCRIPPEN | TCRIPPEN | Disapproved:IECC section R408.2.2 More efficient HVAC equipment performance option. Heating and cooling equipment shall meet the following 1. Greater than or equal to 95 AFUE natural gas furnace and 16 SEER air conditioner. make a different choice on the IECC. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2064802 |
Mechanical (Main) | Original | / | 9/26/2024 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Mechanical (Main) | 2064725 |
Mechanical (Main) | Original | / | 9/24/2024 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2063696 |
Electrical | Original | A | 9/20/2024 | DANIELG | DANIELG | | | Electrical | 2062902 |
Electrical (North) | Original | / | 9/11/2024 | | CHRISTINEH | Location = Electrical (North) by CHRISTINEH | | Electrical (North) | 2058913 |
Construction | Original | A | 9/11/2024 | CHRISTINEH | CHRISTINEH | | | Construction | 2058912 |
Construction (North) | Original | / | 9/11/2024 | CHRISTINEH | CHRISTINEH | In Current Review by CHRISTINEH | | Construction (North) | 2058904 |
Construction (North) | Original | / | 9/11/2024 | | JACKIEP | Location = Construction (North) by JACKIEP | | Construction (North) | 2058846 |
Energy | Original | / | 9/11/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2058834 |
Stormwater | Original | / | 9/11/2024 | SYSTEM | SYSTEM | Parcel 7513402041 is within the Hillside Overlay (HS). Stormwater Review is required. | | Stormwater | 2058833 |
Fire | Original | / | 9/11/2024 | RBD GIS | RBD GIS | Parcel 7513402041 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 2058832 |
Floodplain | Original | N | 9/11/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7513402041) | | Floodplain | 2058831 |