Finished Bin (Main) | Original | / | 10/17/2024 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2074002 |
Energy | Original | D | 10/17/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2074003 |
Plan Coordinator (Main) | Original | / | 10/17/2024 | | SCANNING | Location = Plan Coordinator (Main) by SCANNING | | Plan Coordinator (Main) | 2073964 |
Construction | Original | D | 10/17/2024 | SIERRAC | SIERRAC | Please adjust the Connection Documentation to show that you are using 2023 PPRBC (2021 IBC).
Need to show 130 mph on the Connection Documentation.
Properties over 7,000 ft. are required to have a minimum of 57 psf for the Ground Snow Load. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2073959 |
Construction (Main) | Original | / | 10/17/2024 | SIERRAC | SIERRAC | In Current Review by SIERRAC | | Construction (Main) | 2073929 |
Construction (Main) | Original | / | 10/16/2024 | | SCANNING | Location = Construction (Main) by SCANNING | | Construction (Main) | 2073561 |
Plan Coordinator (Main) | Original | / | 10/16/2024 | | BERTHA | Location = Plan Coordinator (Main) by BERTHA | | Plan Coordinator (Main) | 2073506 |
Electrical | Original | D | 10/16/2024 | BERTHA | BERTHA | Provide floor plan - indicate the location of all electrical gear. Comply with 706.15(E) NEC
Provide conductor type - feeder #4. Provide code compliant conductor.
Provide complete specification for the inverter. Provide specification with NRTL marking.
Complete re-review required. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2073505 |
Out to Review | Original | / | 10/15/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Out to Review | 2072931 |
Out to Review | Original | / | 10/10/2024 | REBECCAM | REBECCAM | Edward walking 719-640-8272 | | Out to Review | 2071226 |
Energy | Original | / | 10/10/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2071224 |
Zoning | Original | N | 10/10/2024 | SYSTEM | SYSTEM | Zoning review is not required for roof-mounted PV solar projects in El Paso County. | | Zoning | 2071223 |
Floodplain | Original | N | 10/10/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7600000063) | | Floodplain | 2071222 |